KEBA

KEBA KeDrive D3-DU Motion control accessories

Product features

• 2 incremental encoder inputs

with 12- or 32-bit resolution

• 2 latch inputs as sink or source input

• Electronic parameter chip

Short description

The MM 240/A is an incremental encoder of the KeConnect C2 product line. This module is attached directly to a CPU

module or can be operated with all KEBA controls by means of bus couplers.

MM 240/A features

• Position measurement: Forward/backward counter of increments by means of tracks A and B

• Single, double, quadruple evaluation

• 32-bit resolution

• Speed measurement through sampling with internal time basis

• Rotary encoder monitoring via zero track information

• Latch function of the counter status via an external latch input 24 V (sink and source)

• Latch function of the counter status via zero pulse

• Sensor failure monitoring of tracks A, B and zero

WESTINGHOUSE 5X00105G14
WESTINGHOUSE 5X00106G01
WESTINGHOUSE 5X00109G02
WESTINGHOUSE 5X00119G01
WESTINGHOUSE 5X00121G01
WESTINGHOUSE 5X00225G01
WESTINGHOUSE 5X00226G01
WESTINGHOUSE 5X00226G02
WESTINGHOUSE 5X00226G03
WESTINGHOUSE 5X00226G04
WESTINGHOUSE 5X00241G01
WESTINGHOUSE 5X00241G02
WESTINGHOUSE 5X00241G04

Incremental encoder

inputs

Number of inputs 2

Resolution 32 bit

Galvanic isolation No

Max. encoder frequency 250 kHz (differential)

Evaluation Single, double and quadruple evaluation configurable, counter function with and without direction evaluation

Max. pulse rate 1 MHz when using quadruple evaluation (differential)

Input range Configurable 5 V differential and 24 V

Position counter

Counter width 32 bit

Speed measurement

Measurement process Gate time measurement with internal 50 MHz cycle

Counter width 24 bit

Minimum detectable speed Pulse duration greater than 0.33 s = speed 0

Encoder supply

Supply 24 V Looped through from 24 V input terminal

Load capacity 100 mA per encoder

Protection Against overload and short circuit

Supply 5 V Produced by 24 V supply via input terminal

Nominal voltage 5.05 V ±4 %

Latch inputs

Number of inputs 2

Response time of latch input 20 μs

Input type Configuration as sink or source input

Galvanic isolation No

Time stamp for latch event

Resolution 1 μs

Max. cycle time 16-bit counter: Unique up to 65 ms cycle time

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. K-bus plug

Depth 100 mm

Weight 135 g

General

Supply voltage 24 V DC from front (nominal voltage tolerance: 19.2 V … 30 V, acc. to EN 61131-2)

24 V DC from K-bus, 5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Connection terminals Open – pitch: 5.08 mm

Max. power consumption K-bus 24 V 0 W

Max. power consumption K-bus 5 V 0.6 W