GE

GE  G60  Generator Protection System

GE  G60  Generator Protection System

The G60 Generator Protection System is part of the Universal Relay (UR) family of products. It is a microprocessor-based

relay that provides protection, monitoring, control, and recording functions for alternating current (AC) generators driven

by steam, gas, or hydraulic turbine. Current, voltage, and frequency protection are provided along with fault diagnostics.

Breaker fail function is provided for up to four breakers.

Voltage, current, and power metering are built into the relay as standard features. Current parameters are available as

total waveform root mean square (RMS) magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).

Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of

storing up to 64 records with programmable trigger, content, and sampling rate, and data logger acquisition of up to 16

channels, with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized

with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port, or using the Precision Time

Protocol (PTP). This precise time stamping allows the sequence of events to be determined throughout the system. Events

can also be programmed (via FlexLogic™ equations) to trigger oscillography data capture that can be set to record the

measured parameters before and after the event for viewing on a computer. These tools significantly reduce

troubleshooting time and simplify report generation in the event of a system fault.

Several options are available for communication. An RS232 port (USB port with the graphical front panel) can be used to

connect to a computer to program settings and monitor actual values. The rear RS485 port allows independent access by

operating and engineering staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports

use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. IEC 60870-5-103. DNP,

and Modbus cannot be enabled simultaneously on this interface. Also only one of the DNP, IEC 60870-5-103. and IEC

60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103 protocol is chosen, the RS485

port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The 100Base-FX or 100Base-TX Ethernet

interface provides fast, reliable communications in noisy environments. The Ethernet port supports IEC 61850. IEC 61850

90-5. Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any

standard web browser (G60 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet

port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4. 2012) when purchased as an option.

GOOSE and secure Routable GOOSE (R-GOOSE) are supported with software options. Process Bus GOOSE is supported with

a hardware module and software options.

With a Process Bus Module that supports IEC 61850-9-2LE and IEC 61869. PRP is supported on two Ethernet ports to IEC

62439. and High-availability Seamless Redundancy (HSR) is supported on four Ethernet ports for dual HSR ring

architecture.

Settings and actual values can be accessed from the front panel or EnerVista software.

The G60 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are

upgradable.

The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)

device numbers.

Table 2-1: ANSI device numbers and functions

Device number Function Device number Function

21P Phase distance backup 51N Neutral time overcurrent

24 Volts per hertz 59N Neutral overvoltage

25 Synchrocheck 59P Phase overvoltage

27P Phase undervoltage 59X Auxiliary overvoltage

27TN Third harmonic neutral undervoltage 59_2 Negative-sequence overvoltage

27X Auxiliary undervoltage 64F Field ground protection

32 Sensitive directional power 64S Sub-harmonic stator ground protection

40 Loss of excitation 64TN 100% stator ground

46 Generator unbalance 67_2 Negative-sequence directional overcurrent

49 Thermal overload protection (RTD) 67N Neutral directional overcurrent

50BF Breaker failure 67P Phase directional overcurrent

50G Ground instantaneous overcurrent 68 Power swing blocking

50N Neutral instantaneous overcurrent 78 Out-of-step protection

50P Phase instantaneous overcurrent 81O Overfrequency

50SP Split phase protection 81R Rate of change of frequency

50/27 Accidental energization 81U Underfrequency

51G Ground time overcurrent 87RGF Restricted ground fault

51PV Phase time overcurrent with voltage

restraint

87S Stator differentia

The following security features are available:

• Password security — Basic security present by default

2

• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The

feature is present by default in the EnerVista software.

• CyberSentry security — Advanced security available using a software option. When purchased, the option is enabled

automatically, and the default Password security and EnerVista security are disabled.

To maximize security, see the UR Family Secure Deployment Guide.

2.2.0.1  EnerVista security

The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to

manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a

substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security

management system is disabled by default to allow the administrator direct access to the EnerVista software after

installation. It is recommended that security be enabled before placing the device in service.

Basic password or enhanced CyberSentry security applies, depending on purchase.

2.2.0.2  Password security

Password security is a basic security feature present by default.

Two levels of password security are provided: command and setting. Use of a password for each level controls whether all

users can enter commands and/or change settings.

Two types of connection security are provided: password entry from local or remote connection. Local access is defined as

access to settings or commands via the front panel interface. This includes both keypad entry and the through a front

panel port. Remote access is defined as access to settings or commands via any rear communications port. This includes

both Ethernet and RS485 connections. These two settings are on by default and apply to all users.

When entering a settings or command password via EnerVista or any serial interface, the user must enter the

corresponding connection password. If the connection is to the back of the G60. the remote password is used. If the

connection is to a front panel port, the local password applies. (These two local and remote password settings are not

shown in the figure.)

Password access events are logged in the Event Recorder.