ALSTOM 029.2285 Controller Module
All device controlled or uncontrolled settings should be avoided as the Fieldbus
communication will start as soon as power is applied, without waiting for the Ethernet
module (9716-4020) to initialise. The Fieldbus slaves will therefore not be under the
control of the GEM80.
Exchange Counter
This unsigned 32-bit variable contains the count of transfers between the GEM80 and
the Fieldbus module.
Presence Indication
The Fieldbus module maintains a bit array of the active devices detected on the
communications link. It is recommended that the application monitors this bit array and
takes appropriate action on loss of I/O. Word 0 bit 0 represents the master itself and
will always contain 0. Word 0 Bit 1represents the device with address 1 etc.
Presence Words 4 to 7 are not required when using DeviceNET and should be ignored.
Module 1 Module 2 Description
| Woodward | 8290-191 |
| Benninger | FU10125A60 |
| ABB | UNS4881b,V.4 3BHE009949R0004 |
| Honeywell | CC-PAIH02 |
| YOKOGAWA | YTA110 |
| STUCKE | SYMAP-BCG 4512 24/1A/PT400V/D1/GC1/G1V400/RU0/C2/0/4/1/2 |
| METSO | ND9106HNT |
| HIRSCHMANN | MM20-Z6Z6Z6Z6SBHH |
| GE | FLC48SXC8V11A |
| Alstom | 29.144463 |
| Woodward | UG‐25+ 8528-300 |
| METSO | XWB11283-900N12 |
| WESTRONICS | SBGA-15P1WM |
| EMERSON | FSFB-S600+ S600P1-0-B-0-0-1 |
| GE | IS200EDISG1AAA |
| Prosoft | RLX2-IFH24E |
Version Buffer
The version buffer is optional; it is disabled by clearing Pn+10 for module 1 or Pn+26
for module 2. When configured, information about the associated module’s hardware
and software is copied to the buffer. The copy occurs once when the controller is
powered-up and again on recompilation of the controller. If insufficient entries are
allocated by the user the report will truncate.
Note. The information presented will be required when contacting the ALSTOM
customer support department.
Fixed V-Table
The GEM80-500 controller has five V-Table entries (V67 to V71 inclusive) reserved for
plug-in module identifiers. The Fieldbus modules will also present their identifiers in
these table entries. The values presented are the lower half of the device type as read
from the Fieldbus module. These values follow on from the modules fitted directly to the
base board. These table entries are reported in the order that they are found by the
driver.
Preface
This section provides a guide to the use of the Hilscher System Software supplied with
the various Fieldbus modules that can be installed in the GEM80-500 Controller.
It illustrates the configuration and down load of a PROFIBUS configuration to a
GEM80-500 PROFIBUS MASTER (Part Number 9723-4020) using the supplied Hilscher
System software.
For other Fieldbus modules the steps taken will be similar, but the selected module and
slave specific data will change.
Detailed information on the operation of this software can be found in the Hilscher
documentation provided on the CD.