ALSTOM 029.155 562 Communication Module
System Configuration
Having correctly installed and configured the Fieldbus modules it is then possible to
configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of
the use of this tool is beyond the scope of this manual, although an operation guide is
included in section 7. For full instructions refer to the Hilscher documentation provided
on the CD.
This Windows based tool can communicate with the Fieldbus module using a serial link
or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the
guide in section 7 follows this route.
The serial link method bypasses the GEM80-500 completely by communicating
directly with the Fieldbus module. This method is suitable for monitoring the network
operation but should not be used for system configuration downloading. As it
communicates directly, new system configurations will be downloaded whether or not
the host GEM80 controller is in a running or halted state.
The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module. As a
result the GEM80 Ethernet module is able to examine the commands sent from the
SyCon tool before passing them to the associated Fieldbus module. The running state
of the host GEM80 is also examined by the Ethernet module, attempts to modify
important system parameters will be refused if the host GEM is in the running state.
This results in an error code of 170 at the SyCon tool. The TCP/IP method is also
suitable for monitoring the network operation.
See section 7 for further information on the operation of the SyCon tool
Exchange Mode
| Woodward | 8290-191 |
| Benninger | FU10125A60 |
| ABB | UNS4881b,V.4 3BHE009949R0004 |
| Honeywell | CC-PAIH02 |
| YOKOGAWA | YTA110 |
| STUCKE | SYMAP-BCG 4512 24/1A/PT400V/D1/GC1/G1V400/RU0/C2/0/4/1/2 |
| METSO | ND9106HNT |
| HIRSCHMANN | MM20-Z6Z6Z6Z6SBHH |
| GE | FLC48SXC8V11A |
| Alstom | 29.144463 |
| Woodward | UG‐25+ 8528-300 |
| METSO | XWB11283-900N12 |
| WESTRONICS | SBGA-15P1WM |
| EMERSON | FSFB-S600+ S600P1-0-B-0-0-1 |
| GE | IS200EDISG1AAA |
| Prosoft | RLX2-IFH24E |
The Exchange Mode LS byte contains the communications state indicator in bit 0. This is
set to 1 if the Fieldbus is performing transfers; otherwise it is cleared to 0. The
remainder of the byte is reserved and is cleared to 0.
The Exchange Mode MS byte contains the process data handshake mode as configured
by SyCon.
• Value = 1. Bus synchronous, device controlled.
• Value = 2. Buffered, device controlled.
• Value = 3. Non-consistent, uncontrolled.
• Value = 4. Buffered, host controlled (recommended).
• Value = 5. Bus synchronous, host controlled.
The recommended setting is buffered host controlled. This will have the least impact on
the controller’s scan rate