FOXBORO

Foxboro 0399143 SY-0301060R SY-1025115C/SY-1025120E Control Module

The Intrinsically Safe I/O Subsystem provides integration between the Pepperl+Fuchs™ (P+F) modular

intrinsically safe remote I/O systems and the I/A Series® system. The Intrinsically Safe Communications

Module (ISCM) enables I/A Series control processors to view the P+F I/O modules as equivalent 200 Series

Fieldbus Modules (FBMs), which can be monitored with standard I/A Series blocks and standard InFusion™

or I/A Series system/control configurator applications such as the InFusion Engineering Environment and the

Integrated Control Configurator.

FEATURES

Intrinsically safe – supports Zone 2. Div. 2 or

Zone 22 (LB-style) environments or Zone 1. or

Zone 21 (FB-style) environments

ISCMs interface the 2 Mbps HDLC Module

Fieldbus to the FCP270 or ZCP270

Up to 46 (for LB-style Zone 2 Applications) or

48 (for FB-style Zone 1 Applications) P+F

intrinsically safe I/O modules supported per

optionally redundant ISCM, with a total of

16 ISCMs supported per I/A Series control

processor (FCP270 or ZCP270); a maximum of

204 modules (ISCMs, I/O modules and

200 Series FBMs) supported per FCP270 and a

maximum of 128 modules supported per

ZCP270. provided the maximum CP Fieldbus

load and intrinsically safe I/O power supply load is

not exceeded

Redundant ISCMs allow either module to control

the process. Role reversal is automatic on

detected failures

Letterbug set through a letterbug module with

rotary switch plugged into the ISCM.

Monitored by standard System Manager or

I/A Series SMDH and FoxView™ displays

“CE” logo marked on product.

OVERVIEW

The Intrinsically Safe I/O Subsystem provides

integration between the Pepperl+Fuchs (P+F)

modular intrinsically safe remote I/O systems and the

I/A Series system. The Intrinsically Safe

Communications Module (ISCM) communicates

between the two systems, as it enables I/A Series

control processors to view supported P+F intrinsically

safe I/O modules as equivalent 200 Series Fieldbus

Modules (FBMs) over the I/A Series 2 Mbps HDLC

Fieldbus. This allows the I/O modules to be

monitored with standard I/A Series blocks and

standard I/A Series or InFusion system/control

configurator applications such as InFusion

Engineering Environment and ICC.

This subsystem supports both the P+F intrinsically

safe I/O modules and their associated base,

extension or redundancy units for Zone 2. Div. 2 or

Zone 22 (LB-style(1)) environments or

Zone 1 or Zone 21 (FB-style(2)) environments.

Optionally redundant ISCMs are mounted directly on

the appropriate P+F unit along with the I/O modules

and power supplies, as shown in Figure 1 and

Figure 2. Only I/O modules can be mounted in the

extension units. Each I/O module can be plugged

into any desired slot on the base or extension unit.

ISCMs and power supplies are required to be

plugged into their own dedicated slots.

GE PCH1026
GE PM33211BP-5-1-3-F
GE PMC-0247RC-282000 350-93750247-282000F
GE PMC422-LAM D2
GE PQMII-T20
GE PRG-MODEM
GE PV2121ED160012CT
GE QPJ-SBR-201
GE R-TPD3
GE REF B3677 G3
GE RS-FS-9001
GE RV33-1

Leave a Reply

Your email address will not be published. Required fields are marked *