Foxboro C0136-HZ Pressure transmitter
FunctionalSpecifications
Communications BusCharacteristics
• CommunicationType
Ethernet
• CommunicationTransmissionRate
10or100Mbps
• CommunicationProtocol
UDP/IPorTCP/IP
• IPAddress
FixedorDHCP
NOTE:FordriverspecificlimitationsonI/OCapacityandDataTypesTransferred,
refertothecorrespondingdriverPSSorUser’sGuide.
I/OCapacity
• Upto64devicesperFBM232maximum(numberofactualdevicesisperformance
dependent)withupto2000DCIconnections.
DataTypesTransferred
• 2-byteor4-bytesignedorunsignedintegers,4-byteIEEEsingle-precisionfloating
values,orbinaryvalues.Automaticconversionforothertypesasimplementedin
thedownloadabledriver.
FastestAllowedECBBlockPeriod
• 500msec
ModuleFieldbus
Communication
CommunicateswithitsassociatedFCM100Et,FCM100E,FCP280.orFCP270viathe
redundant2MbpsmoduleFieldbus.
FBM232Power
Requirements • InputVoltageRange(Redundant)
24VDC+5%,-10%
• Consumption
7W(maximum)
• HeatDissipation
| KUKA | KK67Y-YYYY-050 |
| KUKA | KPS-600/20-ESC |
| KUKA | KRC2/VKRC2 |
| KUKA | KSD1-08 |
| KUKA | KSD1-16 |
| KUKA | KSD1-48 |
| KUKA | MFC2 |
| KUKA | PH1003-2840 |
| KUKA | RDW2 |
| LAM | 810-046015-010 |
| LAM | 810-066590-004 |
| LAM | 810-068158-013 |
| LAM | 810-068158-014 |
7W(maximum)
RegulatoryCompliance,
Electromagnetic
Compatibility(EMC)
EuropeanEMCDirective2014/30/EU
Meets:EN61326-1:2013ClassAEmissionsandIndustrial ImmunityLevels
Regulatory Compliance,
Product Safety
• Underwriters Laboratories (UL) for U.S. and Canada
UL/UL-C listed as suitable for use in UL/UL-C listed Class I, Groups A-D; Division
2; temperature code T4 enclosure based systems when connected to specified
Foxboro DCS processor modules as described in the Standard and Compact 200
Series Subsystem User’s Guide (B0400FA).
Communications circuits also meet the requirements for Class 2 as defined in
Article 725 of the National Electrical Code (NFPA No.70) and Section 16 of the
Canadian Electrical Code (CSA C22.1). Conditions for use are as specified in the
Standard and Compact 200 Series Subsystem User’s Guide (B0400FA).
• European LowVoltage Directive 2014/35/EU and Explosive Atmospheres (ATEX)
Directive 2014/34/EU
DEMKOcertified as Ex nA IIC T4 for use in certified Zone 2 enclosure when
connected to specified processor modules as described in the Standard and
Compact 200 Series Subsystem User’s Guide (B0400FA).
• MarineCertification
ABSTypeApproved and Bureau Veritas Marine certified for Environmental
Category EC31.
Calibration
Requirements
Calibration of the module is not required.