FOXBORO

Foxboro C0136-HZ Pressure transmitter

FunctionalSpecifications

Communications BusCharacteristics

• CommunicationType

Ethernet

• CommunicationTransmissionRate

10or100Mbps

• CommunicationProtocol

UDP/IPorTCP/IP

• IPAddress

FixedorDHCP

NOTE:FordriverspecificlimitationsonI/OCapacityandDataTypesTransferred,

refertothecorrespondingdriverPSSorUser’sGuide.

I/OCapacity

• Upto64devicesperFBM232maximum(numberofactualdevicesisperformance

dependent)withupto2000DCIconnections.

DataTypesTransferred

• 2-byteor4-bytesignedorunsignedintegers,4-byteIEEEsingle-precisionfloating

values,orbinaryvalues.Automaticconversionforothertypesasimplementedin

thedownloadabledriver.

FastestAllowedECBBlockPeriod

• 500msec

ModuleFieldbus

Communication

CommunicateswithitsassociatedFCM100Et,FCM100E,FCP280.orFCP270viathe

redundant2MbpsmoduleFieldbus.

FBM232Power

Requirements • InputVoltageRange(Redundant)

24VDC+5%,-10%

• Consumption

7W(maximum)

• HeatDissipation

KUKA KK67Y-YYYY-050
KUKA KPS-600/20-ESC
KUKA KRC2/VKRC2
KUKA KSD1-08
KUKA KSD1-16
KUKA KSD1-48
KUKA MFC2
KUKA PH1003-2840
KUKA RDW2
LAM 810-046015-010
LAM 810-066590-004
LAM 810-068158-013
LAM 810-068158-014

7W(maximum)

RegulatoryCompliance,

Electromagnetic

Compatibility(EMC)

EuropeanEMCDirective2014/30/EU

Meets:EN61326-1:2013ClassAEmissionsandIndustrial ImmunityLevels

Regulatory Compliance,

Product Safety

• Underwriters Laboratories (UL) for U.S. and Canada

UL/UL-C listed as suitable for use in UL/UL-C listed Class I, Groups A-D; Division

2; temperature code T4 enclosure based systems when connected to specified

Foxboro DCS processor modules as described in the Standard and Compact 200

Series Subsystem User’s Guide (B0400FA).

Communications circuits also meet the requirements for Class 2 as defined in

Article 725 of the National Electrical Code (NFPA No.70) and Section 16 of the

Canadian Electrical Code (CSA C22.1). Conditions for use are as specified in the

Standard and Compact 200 Series Subsystem User’s Guide (B0400FA).

• European LowVoltage Directive 2014/35/EU and Explosive Atmospheres (ATEX)

Directive 2014/34/EU

DEMKOcertified as Ex nA IIC T4 for use in certified Zone 2 enclosure when

connected to specified processor modules as described in the Standard and

Compact 200 Series Subsystem User’s Guide (B0400FA).

• MarineCertification

ABSTypeApproved and Bureau Veritas Marine certified for Environmental

Category EC31.

Calibration

Requirements

Calibration of the module is not required.