Alstom TUG0212 Power Module
Removal of the Drive Data Manager™ (Keypad)
NOTE: To allow the drive to make the necessary safety checks, this removal procedure should always be
followed. A trip may result if this procedure is not followed.
The drive checks if Keypad removal is allowed as the Keypad may have Start/Stop control, or the Keypad
Speed Reference may be active.
To remove the Keypad, continue as shown in Table 2-1.
Do What? How?
1 Ensure the keypad is neither in control of
the Start/Stop nor the keypad Speed
Reference is active
AT DEFAULT:
Simply close DIGIN4. this will select
Remote.
ELSE:
Gain the necessary authorisation
before continuing.
a) Make P34.16 = 1. to set CF116 ON, this
removes the Start/Stop control from the keypad.
b) If a machine bridge, the keypad must
not be either the active reference source or the
backup reference source. The reference sources
are held in P5.01 to P5.05 and are made active
by CF4 to CF7 (P5.07 to P5.10) respectively.
2 Access the keypad removal screen
Press the “esc” key repeatedly.
3 Select “REMOVAL CHECK” Press the “1” key on the keypad
The converter checks to see if the keypad is
allowed to be removed. As well as the above
control and reference checks, P35.01 (Allow
keypad Removal) is also checked.
4 Remove keypad if the screen allows:
| BENTLYNEVADA | 3300/16-11-01-03-00-00-01 |
| BENTLYNEVADA | 3300/20-12-01-03-00-00 |
| BENTLYNEVADA | 84152-01 |
| BERGER LAHR | VRDM 566/50 LNA |
| BERGER LAHR | WPM311.03401 |
| BERGHOF | CDIO 16/16-0,5 |
| BERGHOF | CDIO 16/16-0,5-1131 |
| BERGHOF | CEDIO-S |
| BERGHOF | QAIO16/4-V |
| BERGHOF | RDC2 |
| BERGHOF | RTEMP8/16 |
| BERTHOLD | LB 440-M |
| BETA LASERMIKE | DB 25 PSU |
A message may be flashed disallowing removal
because the keypad is either still in control, still
has active/backup reference
(see step 1 above) or if it is simply disallowed (see
step 3 above).
Table 2-1. – How to Remove the Drive Data ManagerTM (keypad)
2.3 RECALLING A PARAMETER SET FROM A DRIVE DATA MANAGER™
The MV3000e MicroCubicle™ and the MV3000e DELTA AC Drives incorporate a feature to enable the
transfer of parameters from one drive to another via the Drive Data Manager™ (where the Parameter Set
can be saved). This feature is invoked via Parameter P99.16 – Backup Parameter – see Section 6.57.11.
Recalling a Parameter Set from one drive to another is a very powerful and useful feature. However, care
must be taken to ensure that an incorrect Parameter Set in the target drive does not result from copying
the Parameter Set from an inappropriately configured drive, particularly from a drive of different rating from
the source drive. It is therefore recommended that reference be made to the additional guidance in ‘Notes
for Recalling a Parameter Set from the Drive Data Manager™ (Keypad)’ in Section 6.57.11