ABOUT THE MV3000E DRIVE UNIT
The MV3000e range of variable speed AC drives provides powerful features at an economical price. At the
standard level, MV3000e is a simple to use inverter for general-purpose applications for ratings from 22 kW
to 5.8 MW.
At a higher level, open up the parameter menus; add Fieldbus communications, hardware expansion and
programming enhancement facilities, and the power of MV3000e comes alive. Add to this universal control
strategies such as frequency control, closed loop flux vector control and encoderless flux vector control,
and MV3000e easily manages a vast spectrum of industrial applications. A typical MV3000e drive unit is
shown in Figure 1-1 with the optional Drive Data Manager™ fitted.
Figure 1-1. – General View of a Typical MV3000e Drive Unit
In Sinusoidal Front End (SFE) applications an MV3000e Bi-directional Converters are configured to connect
between mains and a DC Link – the DC Link will typically be connected to one or more Machine Bridges. The
SFE is able to control current flow into and out of the mains in order to maintain a constant DC Link voltage,
and as such, allows 4-quadrant operation of the Machine Bridge.
ABOUT THE MV3000E PRODUCT IN SINUSOIDAL FRONT END (SFE) MODE
There are two types of MV3000e products that support operation in SFE mode:
a range of MicroCubicles™ identified by the letter ‘J’ in their product code;
the DELTA product.
In both cases, additional auxiliary circuitry is required to achieve SFE functionality.
The Range of MicroCubicles™ identified by Letter ‘J’ in their Product Code
This range is fitted with internal hardware that allows them to monitor and synchronise to the mains to
which they are connected. When connected to further external auxiliary hardware, they can operate in SFE
mode. The ‘J’ code product does not include a power rectifier circuit. The ‘J’ product is intended for use
either as an SFE or a Machine Bridge. A typical application would include two identical ‘J’ products
connected at their DC terminals, one used as an SFE, and the other as a Machine Bridge.