Alstom 6F00 power module
Ethernet switch
The Ethernet switch shall meet the following standards:
• EMC immunity for industry EN 50082-2 or EN 61000-6-2
Alstom Power Service has successfully used the switches from HMS
Industrial Networks, Sweden and different types of switches from
Hirschman Electronics.
1.4. Ethernet hub
Ethernet hub should not be used in a new installation, because it will
decrease the performance of the network. With a hub in the network it is also
more difficult to calculate the allowed cable lengths.
1.5. Connection to controller
The Ethernet board connection on the controller is of the
following type:
• RJ45 10/100M/bit auto negotiation
1.6. Cables
Cat 5E FTP cables with RJ45 connectors are recommended for the Ethernet
network.
1.7. Ethernet ports and protocols
The following Ethernet ports are used:
• Port 20. 21 for FTP
• Port 80 for HTTP
• Port 502 for Modbus/TCP data
• Port 3 250 for PC-MTU – IP config
• Port 49 200. 49 201 for the master functionality and PC-MTU.
1.8. Ethernet routers
Routers should not be installed in the EPIC III Ethernet network. The PC
MTU and master functionality will not function properly through it.
Network node address lists A list of all nodes with name and addresses
made by ALSTOM Power Service.
Node
PC-MTU
ProMo
ROM
Router
RTU
Subnet
SCR
TCP/IP
TP
T/R
T/R On/Off
| ALSTOM | NRD108034 8RDB44674G01 SA44674.C |
| ALSTOM | NRD109475 8RDA44670G01 SA44670.E |
| ALSTOM | P40 AGILE MICOM P141 |
| ALSTOM | P70035W82V |
| ALSTOM | PIB101C |
| ALSTOM | PIB102A |
| ALSTOM | PIB102A 3BEB0180 |
| ALSTOM | PIB1201A 3BEC0067 |
| ALSTOM | PIB310 |
| ALSTOM | PIB310 3BHB0190 |
| ALSTOM | PIB903 |
| ALSTOM | POS1846 TRVC062333000 CP00000310 |
| ALSTOM | SDK-C0147 12004-101-00 SBS04M17C |
| ALSTOM | SDK-C0148 12003-101-01 SBS05M09B |
| ALSTOM | SDK-C0167-1 12004-08-01 SBS07M076B |
Web browser
Webserver
A node (unit) is a single addressable entity on a
TCP/IP network.
Software used to set-up and monitor an
installation of several EPICs.
A colour graphic software package for process
control.
Read Only Memory.
An active network component that connects
one network to another network.
Remote Terminal Unit gives operators an alpha
numerical and graphical interface to ESP
parameters.
The IP address is divided into three parts to
seperate them from each other a Subnet mask is
used.
Silicon Controlled Rectifier.
Transmission Control Protocol/Internet
Protocol. TCP/IP is a collection of
protocols that control the way data travels from
one node to another across a network.
Twisted Pair (type of cable used e.g. in Ether
net).
Transformer/rectifier.
High voltage On/Off.
A software used to browse or show web (Inter
net) pages e.g. Microsoft Internet Explorer.
A computer (software and hardware) used to
supply client workstations with Web pages.