KEBA SXTPU 16/64 Teach Pendant 3HAC12929-1/01
Product features
• 4 analog voltage inputs usable as differential inputs
or as single-ended inputs
• Resolution 14 bit
• Sensor failure detection
• Electronic parameter chip
Short description
Analog input module KeConnect AI 240/A features four analog voltage inputs that process differential or ratiometric input
signals in the range from ±10 V or 0-10 V with a resolution of 14 bit.
A sensor failure, should it occur, is reported to the higher-level central module and can be evaluated in the application.
This module is attached directly to a CPU module or can be operated with all KEBA controls by means of a bus coupler
Digital outputs
DM 272/A DM 276/A
Number / wiring of outputs 8x source 8x sink
Nominal voltage 24 V DC
Processing time 1 ms
Nominal current of digital outputs 2 A at 50 % simultaneity
Protection facility Short-circuit protection
Max. inductive load 1 J at max 0.2 Hz
Status display Orange LED
Galvanic isolation Yes, from the control electronics and between one another,
electric strength 707 V with isolated ground connection
Dimensions, weight
Height 120 mm
Width 22.5 mm front plate / 32.5 mm incl. K-bus plug
Depth 100 mm
Weight 135 g
General
| RELIANCE ELECTRIC | 0-60023-5 |
| RELIANCE ELECTRIC | 0-60028-2 |
| RELIANCE ELECTRIC | 0-60029-1 |
| RELIANCE ELECTRIC | 0-60031-5 |
| RELIANCE ELECTRIC | 10VV1/F7252 |
| RELIANCE ELECTRIC | 805401-5R |
| RELIANCE ELECTRIC | MD-D4002B |
| RELIANCE ELECTRIC | S-D4006 |
| RELIANCE ELECTRIC | S-D4007 |
| RELIANCE ELECTRIC | S-D4008 |
| RELIANCE ELECTRIC | S-D4012 |
| RELIANCE ELECTRIC | S-D4022 |
| RELIANCE ELECTRIC | S-D4041B |
| RELIANCE ELECTRIC | S-D4043C |
| RELIANCE ELECTRIC | WR-D4005 |
| RELIANCE INSPECTOR | VCIB-06 |
| RENATA | CR2450N |
Supply voltage 24 V DC from front
(nominal voltage tolerance: 19.2 V to 30 V, acc. to EN 61131-2)
24 V DC from K-bus, 5 V DC from K-bus
Overvoltage category II
Protection class III acc. to EN 61131-2
Addressing on K-bus Via 16-digit address switch, on the side
Type of terminals Open – pitch 5.08 mm
Max. power consumption K-bus 24 V 1.9 W
Max. power consumption K-bus 5 V 0.4 W
Analog inputs
Number / type of inputs 4 voltage inputs
Resolution 14 bit
Signal range ±10 V or 0 – Uref (10 V)
Max. measurement signal ±10.4 V
Input type Differential or single-ended
Galvanic isolation No
Reference voltage output 10 V ±2.5 %; max. 20 mA
Scan repeat cycle 1 ms
Input impedance in signal range 10 MΩ
Input filter characteristic – order First order
Input filter limiting frequency 250 Hz
Conversion method Successive approximation
Monotonicity without error codes Yes
Synchroneity control ±13.5 V
Synchroneity suppression > 80 dB
Value of the lowest bit (LSB) 1.3 mV
Maximum permitted continuous load (wit
hout damage) ±30 V
Typ. temp. coefficient measurement error ±5 ppm of scale end value / °C
Max. temp. coefficient measurement error ±20 ppm of scale end value / °C
Largest error at 25 °C ±0.01 % of scale end value