KEBA

Keba RS 091 I RS-091 Power Supply Module 21214 I 2055D-0 Vers. D1.0

Analog inputs (differential or single-ended)

Number of inputs 8

Type Voltage input

Input type Differential (standard setting) or single-ended; freely assignable via software

Signal range Differential: ±10 V; single-ended: 0 – Uref

Reference voltage output Uref 10 V ±2.5 %, max. 20 mA

Max. measurement signal-10.4 V … +10.4 V

Galvanic isolation of the output groups No

Galvanic isolation from the control electronics No

Sensor failure detection Yes

Scan repeat cycle 100 μs

Input impedance in signal range 5 MΩ

Input filter characteristic – order Second order

Input filter transfer frequency 2500 Hz

Digital filters Configurable to: no filter, 500 μs, 1 ms, 5 ms

Resolution 16 bit (±10 V), 15 bit (0 V – Uref)

Conversion method Successive approximation

Monotonicity without error codes Yes

Common mode range ±13.5 V

Common mode rejection ratio > 80 dB

Value of the lowest bit (LSB) 0.325 mV

Maximum permitted continuous load

(without damage) ±30 V

Typ. temp. coefficient measurement error ±5 ppm of scale end value / °C

Max. temp. coefficient measurement error ±20 ppm of scale end value / °C

Largest error at 25 °C ±0.02 % of scale end value

Analog outputs

Number of outputs 6

Type Voltage output

Signal range ±10 V

Galvanic isolation of the output groups No

Galvanic isolation from the control electronics No

Permanently short-circuit proof Yes

Conversion cycle 100 μs

Digital resolution 12 bit

Value of the lowest bit (LSB) 5.22 mV

Monotonicity Yes

Load resistance ≥ 1000 Ω

Largest capacitive load ≤ 10 nF

SCHNEIDER RXZE1M114M
SCHNEIDER SDC40
SCHNEIDER STBAVO0200
SCHNEIDER STBDAI7220
SCHNEIDER STBDAO8210
SCHNEIDER TCSESM043F2CS0
SCHNEIDER TFTX11702
SCHNEIDER TM258LD42DT
SCHNEIDER TSX07301012
SCHNEIDER TSX07301028
SCHNEIDER TSX07311612
SCHNEIDER TSX07311622
SCHNEIDER TSX07311628
SCHNEIDER TSX07311648
SCHNEIDER TSX07312422

Settling time when changing over the full range ≤ 100 μs

Typ. temp. coefficient analog output error ±20 ppm of scale end value / °C

Max. temp. coefficient analog output error ±30 ppm of scale end value / °C

Largest error at 25 °C ±0.15 % of scale end value

Temperature inputs J, K, L, N

Number of inputs 8

Galvanic isolation Yes, from the control electronics and between one another

Electric strength 500 V AC

Sensor failure detection Yes, underflow

Thermoelement types J, K, L, N

Measurement ranges

Type J (Fe-CuNi): -100 °C … +700 °C

Type K (NiCr-Ni): -100 °C … +1000 °C

Type L (FeCu-Ni): -100 °C … +700 °C

Type N (NiCrSi-NiSi): -100 °C … +1000 °C

Measurement principle Integrated

Measurement interval Configurable: 20 / 40 / 100 ms

Mains frequency Configurable: 50 / 60 Hz

Input resistance 10 MΩ

Maximum resistance value

of the thermoelement 50 Ω

Resolution of the measurement process 16 bit

Connections Pluggable connection terminals pitch 5.08. gold-plated contacts

Intrinsic deviation ±2.5 °C max. absolute measurement deviation over the entire measurement range (±0.5 °C

typical), at 25 °C ambient temperature at the module

Operational deviation

±1 % of measurement value or ±2.5 °C absolute. The larger of the two values applies.

Absolute measurement deviation under reference conditions: Ambient temperature of the modu

le between 0 °C and 55 °C, temperature measurement range between 0 °C and 500 °C

Precision of terminal temperature sensor ±1 °C max. absolute measurement deviation at 0 °C to 70 °C ambient temperature (±0.5 °C

typical)

Precision with internal

terminal temperature compensation ±2 °C after 30 minutes, with natural convection

Precision with external compensation

with TE 220/A

With the optimized positioning of the external sensor (TE 220/A), the error can be minimized to

±0.5 °C (typical) through terminal temperature compensation

Thermal settling time After 15 – 30 minutes, the measurement result is stable and within the specified tolerances

EtherCAT interface

Number 2

Data transmission rate 100 Mbit/s

K-bus interface

Function for the direct connection of K-bus modules