FOXBORO RH924YF – Foxboro Process Module
Static Pressure Effect on Differential Pressure
The zero and span shift for a 7 MPa, 1000 psi,
change in static pressure is:
ZERO SHIFT (a)
Span Code
Zero Shift-Static Pressure Effect
±0.30% URL (b)
B and C
±0.10% URL
±0.50% URL (b)
±0.50% URL
a. Can be calibrated out by zeroing at nominal line
pressure.
b. Per 3.5 MPa (500 psi) for Span Codes A and D.
SPAN SHIFT
±0.25% Reading (±0.030% for Span Code A)
Vibration Effect
Total effect is ±0.2% of URL per “g” for vibrations in
the frequency range of 5 to 500 Hz; with double
amplitudes of 6.3 mm (0.25 in) in the range of 5 to 15
Hz, or accelerations of 3 “g” in the range of 15 to 500
Hz, whichever is smaller, for transmitters with
aluminum housings; and with double amplitudes of
6.3 mm (0.25 in) in the range of 5 to 9 Hz, or
accelerations of 1 “g” in the range of 9 to 500 Hz,
whichever is smaller, for transmitters with 316 ss
housings.
| PELCO | PA30-0065-00-A1 |
| PENTEK | FILTER 3F11 800000919 |
| PENTEK | PC.8297023L 320-71400 |
| PEPPERL+FUCHS | 2108HAT |
| PEPPERL+FUCHS | HID2082 |
| PEPPERL+FUCHS | RSD-CI-EX8 |
| PEPPERL+FUCHS | RSD-TI-EX8 |
| PERITEK | AC7-00712-1113 |
| PHILIPS | 958481223220 |
| PHILIPS | 958481223223 |
| PHILIPS | 958481320100 LCB |
| PHILIPS | 958481320201 PROC PLUS |
| PHILIPS | 958481320201 PROC+ |
| PHILIPS | 958481320400 PIF |
| PHILIPS | 958481321200 PD216 |
Fill Fluid
Silicone Oil or Inert FC43
Process Wetted Materials
PROCESS CONNECTION
316L ss, cs, Monel, or Nickel alloy, or PVDF
(Kynar)
SENSOR DIAPHRAGM
316L ss, Co-Ni-Cr, Monel, Tantalum, Nickel
alloy, or Gold-Plated 316L ss, as specified
GASKET
Glass-filled PTFE
Pressure Seal Diaphragm Material
Varies with pressure seal selected. See
PSS 2A-1Z11 A.
Dimensions
Refer to “DIMENSIONS – NOMINAL” on page 36
and to Dimensional Print DP 020-447.
Approximate Mass (with Process Connectors)
4.2 kg (9.2 lb) – with Traditional Structure
Add 0.1 kg (0.2 lb) – with Low Profile Structure LP1
Add 0.8 kg (1.8 lb) – with Low Profile Structure LP2
Add 1.1 kg (2.4 lb) – with 316 ss Housing
Transmitter prepared for Foxboro Model Coded Remote Mount Seals (b)
Transmitter prepared for Remote Seals on Both HI and LO Sides, Silicone Fill in Sensor
Transmitter prepared for Remote Seals on Both HI and LO Sides, Inert Fill in Sensor
S1 (c)
S2 (c)
Transmitter prepared for Remote Seal HI Side, 1/2 NPT Connector LO Side, Silicone Fill in Sensor
Transmitter prepared for Remote Seal HI Side, 1/2 NPT Connector LO Side, Inert Fill in Sensor
S3 (c)
S4 (c)
Transmitter prepared for Remote Seal LO Side, 1/2 NPT Connector HI Side, Silicone Fill in Sensor
Transmitter prepared for Remote Seal LO Side, 1/2 NPT Connector HI Side, Inert Fill in Sensor
S5 (c)
S6 (c)
5. Transmitter Prepared for Foxboro Model Coded Direct Connect Seals (b)
PSFLT, PSSCT, or PSSST Direct Connect Seal on HI Side; 1/2 NPT Process Connector LO Side; Silicone Fill
PSFLT, PSSCT, or PSSST Direct Connect Seal on HI Side; 1/2 NPT Process Connector LO Side; Inert Fill
PSFLT, PSSCT, or PSSST Direct Connect Seal on HI Side; Remote Seal with Capillary LO Side; Silicone Fill
PSFLT, PSSCT, or PSSST Direct Connect Seal on HI Side; Remote Seal with Capillary LO Side; Inert Fill
6. Transmitter Prepared for non-Foxboro Seals
Remote Seals on High and Low Sides; Silicone Fill in Sensor
Remote Seals on High and Low Sides; Inert Fill in Sensor
Remote Seal on High Side and 1/2 NPT Connector on Low Side, Silicone Fill in Sensor
Remote Seal on High Side and 1/2 NPT Connector on Low Side, Inert Fill in Sensor
Remote Seal on Low Side and 1/2 NPT Connector on High Side, Silicone Fill in Sensor
Remote Seal on Low Side and 1/2 NPT Connector on High Side, Inert Fill in Sensor
Span Limits
kPa inH2O mbar
0.12 and 7.5 0.5 and 30 1.2 and 75
0.87 and 50 3.5 and 200 8.7 and 500
7 and 210 28 and 840 70 and 2100
MPa psi bar
0.07 and 2.1 10 and 300 0.7 and 21
0.7 and 21 100 and 3000 7 and 210
Process Connector Type (Material Same as Process Cover Material) (f)
See below:
For d/p: No connectors; both covers tapped for 1/4 NPT (316 ss only, no side vents)
Flange Mount Hi Side: 1/2 NPT, 316 ss Process Connector on Lo Side (F1 and F2 only)
Flange Mount Hi Side: No connectors; both sides prepared for seals (F3 and F4 only)
Two Remote Seals: No connectors; both covers tapped for capillary connection (S1. S2. SA, SB only)
One Remote Seal: 1/2 NPT, 316 ss Process Connector on Side Opposite Seal (S3 to S6. SC to SF only)
1/4 NPT, Not with Structure Codes 46 to 49. 78. 79. or pressure seals
1/2 NPT, Not with Structure Codes 78 or 79. or pressure seals
Rc 1/4. Not with Structure Codes 46 to 49. 78. 79. or pressure seals
Rc 1/2. Not with Structure Codes 78 or 79. or pressure seals
1/2 Schedule 80 Welding Neck, Not with Structure Codes 46 to 49. 78. 79. or pressure seals
None; PVDF Insert tapped for 1/2 NPT/Process Inlet on Side of 316 ss Process Covers (only with 78/79 above)
Conduit Connection and Housing Material
1/2 NPT Conduit Connection, Aluminum Housing
PG 13.5 Conduit Connection, Aluminum Housing (With Electrical Safety Code D only)
1/2 NPT Conduit Connection, 316 ss Housing
PG 13.5 Conduit Connection, 316 ss Housing (With Electrical Safety Code D only)
M20 Conduit Connection, Both Sides, Aluminum Housing (With Electrical Safety Code D only)