FOXBORO

Foxboro 130K-N4-LLPF Process Controller

Exceptional Value

The combination of small size, light weight, direct

mounting, standard materials, and wide

measurement capability with high performance

make this an exceptionally cost effective solution for

process pressure measurement.

Direct Process Mounting

Because of their light weight and external threaded

connection, these transmitters can be installed

directly on process piping without mounting

brackets. However, for unique requirements, an

optional bracket is offered and connection can be

made to the standard 1/4 NPT internal thread.

Wide Rangeability

Three absolute pressure versions are offered to

allow spans from 7 to 21 000 kPa (1 to 3000 psi),

and four gauge pressure versions are offered to

allow spans from 7 to 42 000 kPa (1 to 6000 psi).

Refer to IGP20 Transmitter for gauge pressure

vacuum service.

316L ss, Nickel alloy, and Co-Ni-Cr Process

Wetted Parts

With process connection of 316L ss or Nickel

alloy(1), and sensor diaphragm available in either

316L ss, Nickel alloy, or highly corrosion resistant

Co-Ni-Cr, this transmitter is an excellent choice for

the vast majority of process pressure

measurements.

Span and Range Limits for IAP10 and IGP10 Transmitters

Span Limit

Code

Span Limits

MPa

psi

Figure 5. Direct-Connected Transmitter

(Flameproof Version Shown on Left)

High Gauge Pressure Versions

Three high gauge pressure versions with upper

range limits of 52. 105. and 210 MPa (7500. 15 000.

and 30 000 psi) are available in the IGP10 line. Refer

to PSS 2A-1C13 F for detailed specifications.

Sanitary and Pulp and Paper Versions

These transmitters are also available with integral

process connections for use in sanitary and pulp

and paper installations. See PSS 2A-1C13 K and

PSS 2A-1C13 L, respectively.

Flameproof Design

The IAP10 and IGP10 flameproof versions are

designed to meet Agency flameproof and zone

requirements.

Maximum Overrange and Proof Pressure Ratings for IAP10 and IGP10 Transmitters

Span Limit

Code

MKS 220CD-00001C2B
MKS 220DD-00100D2B
MKS 223BD-00001AAB
MKS 683B-23795
MKS T3BIB-29916
MM MM-6180PXX 95191
MODICON 140CRP93100
MODICON AS-B875-002
MODICON AS-BADU-204
MODICON AS-J890-002
MODICON AS-S908-120 AS-9385-002
MODICON NW-BM85D002
MODICON PC-L984-785
MOLEX 85003-0567

Maximum Overrange Pressure Rating (a)

Proof Pressure Rating (a) (b)

a. Values listed are in absolute or gauge pressure units, as applicable. Maximum overrange pressure is the maximum pressure that

may be applied without causing damage to the transmitter.

b. Proof pressure ratings meet ANSI/ISA Standard S82.03-1988. Unit may become nonfunctional after application of proof pressure.

c. Span Limit Code F is applicable to IGP10 Transmitter only. Also not available if pressure seals are selected.

Accuracy (Includes Linearity, Hysteresis, and

Repeatability)

If Span is:

Accuracy in % of Span is:

≥ 6.7% of URL

< 6.7% of URL

±0.1%

± 0.10

+

( ) 0.0067

( ) URL

NOTE

 ————–

Span

 

Accuracy is at Reference Operating Conditions;

Zero-based Calibrations; Co-Ni-Cr or 316L ss

sensor with silicone fluid; URL = upper range

limit; and span = calibrated span.

Stability

Long term drift is less than ±0.05% of URL per year

over a 5-year period.

Calibration Frequency

The calibration frequency is five years. The five

years is derived using the values of allowable error

(% span), TPE (% span), performance margin

(% span), and stability (% span/month); where:

Performance Margin

Stability

Calibration Frequency —————————————————— M

Ambient Temperature Effect

Total effect for a 28°C (50°F) change within Normal

Operating Condition limits is:

Span Code

Ambient Temperature Effect

C, D, E, and F (a)

±(0.08% URL + 0.05% Span)

a. Span Code F applicable to IGP10 only.

NOTE

For additional ambient temperature effect when

pressure seals are used, see PSS 2A-1Z11 A.

Vibration Effect

Total effect is ±0.2% of URL per “g” for vibrations in

the frequency range of 5 to 500 Hz; with double

amplitudes of 6.3 mm (0.25 in) in the range of 5 to 15

Hz, or accelerations of 3 “g” in the range of 15 to 500

Hz, whichever is smaller, for transmitters with

aluminum housings; and with double amplitudes of

6.3 mm (0.25 in) in the range of 5 to 9 Hz, or

accelerations of 1 “g” in the range of 9 to 500 Hz,

whichever is smaller, for transmitters with 316 ss

housings

Leave a Reply