Foxboro P0916VB Termination Cable
MODULE FIELDBUS COMMUNICATION
The ISCM supports the redundant 2 Mbps HDLC
module Fieldbus to communicate with the FCP270
or ZCP270 (via optionally redundant FCM100E/Et
modules), as shown in Figure 5 and Figure 6.
The FCP270 can connect to both P+F I/O modules
and 200 Series FBMs, provided the appropriate
sizing constraints are followed (detailed in the Field
Control Processor 270 (FCP270) Sizing Guidelines
and Excel Workbook (B0700AV) and Z-Module
Control Processor 270 (ZCP270) Sizing Guidelines
and Excel Workbook (B0700AW)). To connect
simultaneously to 200 Series FBMs, the FCP270
must use the FEM100 to add up to three Expanded
Fieldbuses for these FBMs.
| GE | VMIVME-7698 |
| GE | VMIVME-7740-850 350-007740-850 L |
| GE | VMIVME-7750 |
| GE | VMIVME-7750 VMIVME-7750-740001 350-027750-740001 P |
| GE | VMIVME-7750 VMIVME-7750-760000 350-027750-760000 N |
| GE | VMIVME-7750 VMIVME-7750-834 350-027750-834 D |
| GE | VMIVME-7750-740000 350-027750-740000 |
| GE | VMIVME-7750-746000 350-027750-746000 |
| GE | VMIVME-7750 |
| GE | VMIVME-7807 |
| GE | VMIVME-7807 VMIVME-017807-414001 350-0001007807-414001 D |
The FCP270. 200 Series FBMs and their
support hardware are suitable for Zone 2 or
Class I, Div.2 areas only. Installing this
equipment in a Zone 1 area requires the
employment of additional protection
methods and is your responsibility to
implement.
NOTE
When an FCP270 is connected to both P+F
I/O modules and 200 Series FBMs via an
FEM100. the Expanded Fieldbus 1 cannot
be connected to any FBM baseplates (must
be left disconnected), and Expanded
Fieldbus 2 can only be used with FBM
baseplates addresses 1. 2 and 3 to avoid
letterbug addressing conflicts. Expanded
Fieldbus 2 and 3 can connect and address
all four baseplates (0 through 3).
For more information on the FEM100 and the
Expanded Fieldbus, refer to FEM100 Fieldbus
Expansion Module (PSS 21H-2Y16 B4).
To connect to a ZCP270. the ISCM connects to an
FCM100E/Et module, which in turn connects to the
ZCP270 over a 100 Mbps Ethernet fiber optic
network (via The MESH control network).
For Zone 2 (LB-style) applications, a maximum of
60 meters (197 ft) of standard fieldbus cable may be
used between the FCP270 or FCM100E/Et and the
remote I/O system. For Zone 1 (FB-Style)
applications, a maximum of 152 meters (500 ft) of
high quality twinaxial cable may be used between the
FCP270 or FCM100E/Et and the remote I/O system