Foxboro FBM201D Analog Input Interface module
Zone 2 (LB-Style) P+F Intrinsically Safe Units
and Support Equipment To Support the ISCM
Table 3 lists the supported Zone 2 (LB-Style) I/O
base, redundancy and extension units and their
associated enclosures and power supplies.
Table 3. P+F Intrinsically Safe Units and Support Equipment To Support the ISCM (Zone 2. LB-Style)
P+F Model No.(a)
Description
LB 9022 F
Zone 2 Redundancy Base Unit with 22 slots for Zone 2 (LB-style) applications
LB 9024
LB 9547-S70-F
Zone 2 Extension Unit with 24 slots
Zone 2 stainless steel enclosure with 46 slots for Zone 2 (LB-style) applications
LB 9006 C
Zone 2 power supply – 24 V dc input
NOTE: Two LB 9006 C power supplies are required for each base and extension
unit. Where redundant ISCMs are also installed, a third power supply is required in
each unit to support redundancy
Zone 1 (FB-Style) P+F Intrinsically Safe Units and Support Equipment To Support the ISCM
Table 4 lists the supported Zone 1 (FB-Style) I/O base, redundancy and extension units and their associated
enclosures and power supplies.
Table 4. P+F Intrinsically Safe Units and Support Equipment To Support the ISCM (Zone 1. FB-Style)
P+F Model No.(a)
Description
FB 9224-PG0
Zone 1 GRP enclosure with 24 slots
FB 9225-PG0
FB 9248-PG0
FB 9249-PG0
FB 9224-S60
Zone 1 GRP enclosure with 24 slots (redundant)
Zone 1 GRP enclosure with 48 slots
Zone 1 GRP enclosure with 48 slots (redundant)
Zone 1 stainless steel enclosure with 24 slots
FB 9225-S70
FB 9248-S70
FB 9249-S80
FB 9205 D
FB 9206 D
FB 9215 B
FB 9216 B
Zone 1 stainless steel enclosure with 24 slots (redundant)
Zone 1 stainless steel enclosure with 48 slots
Zone 1 stainless steel enclosure with 48 slots (redundant)
Zone 1 power supply – 230 V ac / boost power for DO modules FB621x
Zone 1 power supply – 24 V dc input
Zone 1 power supply – 230 V ac input
Zone 1 power supply – 115 V ac input
FB 9224-PG0 Zone 1 GRP enclosure with 24
slots
1 socket for communication interface FB 820X
1 socket for power supply FB 92XX
24 sockets for I/O modules
Cable glands (plastic)
2 x M20 for power supply
2 x M20 for bus cable
1 x M20 for service bus cable
1 x M20 for later expansion for redundancy
24 x M16 for 24 I/O cables
24 x M16 blanking plugs
Terminals for mains connection and bus VBG4 protected.
FB 9225-PG0 Zone 1 GRP enclosure with 24
slots (redundant)
2 sockets for communication interface FB 820X
2 sockets for power supply FB 92XX
24 sockets for I/O modules
Cable glands (plastic)
2 x M20 for power supply
2 x M20 for bus cable
1 x M20 for service bus cable
1 x M20 for expansion for redundancy
24 x M16 for 24 I/O cables
24 x M16 blanking plugs
Terminals for mains connection and bus VBG4 protected.