Foxboro FBM218 Input Interface Module
Cable Entry
Bottom cable entry for power, communication, and field cables is through customer
supplied cable glands that maintain the enclosure protection classification, or optional
factory fitted Multi Cable Transit (MCT).
Modular Baseplate Mounting
The enclosure contains two 8-position standard 200 Series modular baseplates for
Foxboro DCS Fieldbus Modules (FBMs), and two 2-position baseplates for the
FCM2F10s. These are mounted on two vertical DIN rails as shown in Figure 1. page
7. The FBMbaseplates include signal connectors for the FBMs, redundant
independent DC power connections, system cable connections, module fieldbus
connections, and time synchronization connections.
For more information on the modular baseplates, see Standard 200 Series
Baseplates (PSS 41H-2SBASPLT).
| MOOG | G771K208A |
| MOOG | G771K208A |
| Honeywell | TC-RPCXX1 |
| MOOG | D661-4642 |
| ALSTOM | PIB100G MV7306P22 |
| ALSTOM | PIB102A MV7306P23 |
| ALSTOM | PIB310 MV7306P24 |
| ALSTOM | PIB201A |
| ALSTOM | PIB701 MV7306P16 |
| Yokagawa | AAI841-H00-S2 |
| Yokagawa | ADV151-P00-S2 |
| Yokagawa | ADV551-P00-S2 |
| Yokagawa | ALR121-S00-S1 |
| Yokagawa | ALF111-S00-S1 |
| Yokagawa | CP451-10-S2 |
Field Termination Assemblies
Termination Assemblies (TAs) are installed on the DIN rails mounted at the sides of
the FBM baseplates. The Universal I/O modules are connected to the TAs with pre
installed system cables.
The TAs are supplied with redundant 24 V DC, protected by fuses that are monitored
by the Fuse Monitoring Unit (FMU).
The enclosure is shipped with TAs fitted with passive feed-through signal conditioners
which you can replace with the signal conditioners listed in the section Termination
Assemblies and Signal Conditioners, page 8.
Power Distribution Architecture
The enclosure provides a redundant 24 V power system using two FPS480-24 power
supplies fed by independent sources. Power wiring is routed through the bottom of the
enclosure. The input power connects to the primary and secondary entry terminal
blocks for main and backup power.
Electrical fuses are monitored by the Fuse Monitoring Unit (FMU) and an open fuse
indication from the FMU is wired into the Enclosure Monitoring Unit (EMU) through the
Alarm Distribution Assembly.
Grounding
All enclosure structural elements are integrally grounded by the enclosure design to
meet the appropriate industry regulations and standards. The enclosure is equipped
with two instrument earth bars. It also has a protective connection point at the outside
bottom of the enclosure for customer grounding purposes. Field wiring shields can be
terminated either to the Terminal Assemblies or to the instrument ground bus bar.
Spare signal wires and shields can be terminated either to the Terminal Assemblies or
to the instrument ground bus bar
Enclosure Diagnostic Alarms
The EMUprovides an alarm for power supply failure detection, fuse failure detection
via the FMU, door open, fan deterioration, and enclosure over temperature. The EMU
provides a composite diagnostic alarm from a graduated analog signal that indicates
individual alarms and is prewired to a Universal I/O module channel for indication and
alarm.
Enclosure Security
The enclosure can be physically locked with a customer-supplied padlock to provide
physical security. The enclosure is also fitted with a door open switch that is alarmed
via the Enclosure Monitoring Unit to alert plant personnel