Triconex

TRICONEX Jan-62 – Control system module

Three types of cables can be used with the Tricon:

• Interface Cables

• Fanned-Out Cables

• Special Cables (Relay Loopback)

Interface Cables

Interface cables are packaged with all termination panels. Each interface cable has a female

connector on one end for connection to the male connector on a Tricon chassis backplane. The

opposite end has a keyed male connector for connection to a termination panel.

Although the standard length of all interface cables is 10 feet (3 meters), you may order any

length cable up to 90 feet (27.4 meters) in 10-foot increments using the last two digits of the

termination panel’s model number to specify length in feet. For example, specify 9xxx-x50 if you

want a 50-foot (15 meter) cable instead of the standard 10-foot (3-meter) cable.

Fanned-Out Cables

Fanned-out cables are a lower-cost alternative to using external termination panels. Fanned-out

cables allow you to marshal field signals in a separate enclosure up to 99 feet (30 meters) from

a Tricon. One end of a fanned-out cable has a female connector that connects to a Tricon chassis

backplane. The other end of the cable contains 50 fanned-out leads, each individually labeled

with its corresponding connector pin number.

Each fanned-out cable has the following characteristics:

Overview

This chapter provides information for determining field termination options using module part numbers or module types, and

it describes how to install and remove termination panels and fanned-out cables.

Determining Field Termination Options by Module Part Number

This table identifies which termination products you can use with a given I/O module. Match your module part number in the

left column to termination options on the right.

Table 1 Termination Product Options (Listed by Module Part Number)

Module

Part # Module Description Commoned

Term Panels

Non-Common.

Term Panels

Basic

Term Panels

Nonincendive

Term Panels

RG 1.180

Term Panels

Fanned-out

Cables

Bypass

Panels

ERT Loop-Back

Cables/Panels

3501E

3501T

DI, 115 VAC/VDC, 32 pts. 9561-810 9561-110 9551-110 n/a n/a 9101-010 n/a 9141-010

3502E DI, 48 VAC/VDC, 32 pts. 9562-810 n/a 9552-610 n/a n/a 9101-010 n/a 9142-010

3503E DI, 24 VAC/VDC, 32 pts. 9563-810

9563-910

n/a 9553-610 9572-610 n/a 9101-010 BP9228-010 9143-010

3504E DI, 24/48 VDC,

non-isolated, 64 pts.

9566-810. 24V

9565-810. 48V

n/a

n/a

9750-310. 24V

9750-410. 48V

9570-610.

24V

n/a

n/a n/a

n/a

BP9229-010

n/a

n/a

n/a

3505E DI, 24 VDC, low threshold,

32 pts.

9563-810

9563-910

n/a 9553-610 9572-610 n/a 9101-010 BP9228-010 9143-010

3510 PI, 20-20.000 Hz, 8 pts. n/a n/a 9753-110 n/a n/a n/a n/a n/a

3511 PI, 20-20.000 Hz, 8 pts. n/a n/a 9753-110 9793-110 9794-110 n/a n/a n/a

3515 Pulse totalizer, 24 VDC,

32 pts.

n/a n/a 9753-110 9572-610 n/a n/a n/a n/a

3564 DI, 24 VDC, single, 64 pts. 9566-710 n/a 9553-610 9571-610 n/a 9101-010 n/a n/a

3601E DO, 115 VAC, 16 pts. 9661-610

9663-610

9661-110

9664-110

9651-110 n/a n/a 9101-010 n/a 9670-110

9670-610

3601T DO, 115 VAC, 16 pts. 9663-610 9664-110 n/a n/a n/a n/a n/a n/a

3603B DO, 120 VDC, 16 pts. n/a 9251–210 n/a n/a n/a n/a n/a n/a

• PVC outer covering

• 56-pin connector at one end

• 50 stranded, stripped, tinned and labeled 22-gauge leads at opposite end

Fanned-out cables should only be used with digital input and digital output modules. They are

not certified for use with analog signals. Contact the Triconex Customer Support Center if you

need a fanned-out cable for handling analog signals.

Although the normal length of all fanned-out cables is 10 feet (3 meters), any length cable can

be ordered up to 99 feet (30 meters) in 1-foot increments, using the last two digits of the cable

model number to specify the length in feet. For example, the model number 9101-050 specifies

a 50-foot cable instead of the normal 10-foot cable.

Special Cables (Relay Loopback)

If your application requires a special cable, it must be ordered separately. For example, if you

want to verify relay activation on a relay termination panel using a digital output module, you

must order a relay loopback cable to connect between the relay termination panel and a digital

Leave a Reply