Triconex 4000043-310 Analog Input Cable Assembly
Bypass Term Panels
This section describes bypass term panels, which are available for 32-point and 64-point digital
input modules.
Model numbers of these term panels are:
• BP9228-010 (24 V, bypass, 32 pts., for 32 pt. modules)
• BP9229-010 (24 V, bypass, 32 pts., for 64 pt. modules)
This figure represents a typical 32-point bypass termination panel that is compatible with
32-point digital input modules.
Compatible Modules
This table describes pulse input and pulse totalizer input modules compatible with 9753–110.
Table 47
Modules Compatible with 9753–110
Module Part
Number
Points per
Module
Module Description
3510
8
20 Hz to 20 KHz pulse input, non-commoned, AC-coupled, 50 ms
typical input update rate
3511
8
20 Hz to 20 KHz pulse input, non-commoned, AC-coupled, 25 ms
typical input update rate
3515
32
0 to 1 kHz pulse totalizer input, non-commoned
BP9228-010 (24 V, bypass, 32 pts., for 32 pt. modules)
Termination panel BP9228-010 is compatible with 24 VAC/VDC and 24 VDC digital input
modules, has 32 input points, and is supplied with two interface cables.
The panel is 3.5 inches high, 4.0 inches deep, and 19 inches wide (88.9 mm x 101.6 mm x 482.5
mm) and complies with EIA Standard RS-310-C. Each cable is keyed to the appropriate digital
input module. P1 connects points 1-16. and P2 connects points 17-32. A 6-terminal barrier strip
has terminals for redundant 24 VDC power with diode ORing provided on the panel. Each
screw terminal accepts either #6 ring-lug terminals, or 24-gauge to 12-gauge (0.2 mm2 to
3.3 mm2) wires.
Specifications
This table describes specifications for BP9228-010.
Table 48
Specifications for Term Panel BP9228-010
Feature
Description
Panel type
Points
Bypass
32