TRICONEX 7400212-100 Safety I/O Module
Installing a Fanned-Out Cable
This procedure explains how to install a fanned-out cable.
Procedure
1 Set up the Tricon chassis and install the I/O modules as described in the Planning and
Installation Guide for Tricon v9–v10 Systems.
2 Remove incoming power from the Tricon system (optional).
3 Re-key the female connector on the fanned-out cable to match the male connector on the
Tricon backplane. For instructions, see Appendix A, Re-Keying Connectors.
4 Attach the fanned-out cable connector to the panel connector that is above the
corresponding I/O module.
5 Connect the fanned-out cable wires to the field devices or marshaling termination.
6 Perform a static check of the wiring.
7 If Tricon power was removed in step 1. restore power to the Tricon system.
8 Apply field power to the devices connected to the fanned out cable.
9 Verify the connection of all I/O points to the appropriate field wiring by using the
TriStation software to inspect input points and force output points.
Note To inspect input points and force output points, see the Planning and Installation
Guide for Tricon v9–v10 Systems.
10 Load and test the control program using TriStation.
If you need additional information on how to install fanned-out cables, contact the IPS Global
Client Support (GCS) center.
Removing or Replacing a Fanned-Out Cable
This procedure explains how to remove or replace a fanned-out cable.
Procedure
1 Remove field power from the termination panel.
2 Detach the fanned-out cable connector that is above the corresponding I/O module.
3 Detach the fanned-out wires from the field termination panel or the field devices
16-Point Commoned Digital Input Term Panels
This section describes 16-point commoned digital input term panels. Model numbers of these
term panels are:
• 9561-810 (115 V, commoned, 16 pts.)
• 9562-810 (48 V, commoned, 16 pts.)
• 9563-810 (24 V, commoned, 16 pts.)
• 9563-910 (24 V, commoned, resistor protected, 16 pts.)
This figure represents a typical 16-point commoned digital input termination panel with fuses
and blown-fuse indicators.