Triconex

3625A | Triconex | Digital 24VDC Output Module

9566-710 (24 VDC, commoned, 32 pts.)

Termination panel 9566–710 is compatible with 24 VDC digital input modules and has 32 input

points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a

180 ohm current-limiting resistor.

The modules compatible with 9566–710 have 64 points, which means you must use two term

panels for each digital input module.

Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply

the labels, see Appendix F, Panel Labels.

Specifications

This table describes specifications for 9566–710.

Table 30

Specifications for Term Panel 9566–710

Feature

Description

Panel type

Commoned

Points

32

Compatible Modules

This table describes digital input modules compatible with 9566–710.

Table 31

Modules Compatible with 9566–710

Module Part

Number

Points per

Module

Module Description

3564

64

24 VDC, commoned, single

Field Wiring Diagrams

This figure illustrates how to connect a 64-point digital input module and a 9566–710 to the field

Simplified Schematics

This is a simplified schematic of a typical 64-point commoned 24 VDC digital input module with

a 9566-710 (1 of 64 module points shown).

TERMINATION PANEL

180 Ohms

CABLE

BACKPLANE

64-POINT DIGITAL INPUT MODULE

to

spare

Test ON Relays

(opto-isolated)

PS1

PS2

to

ABB IMASI02
ABB IMASI03
ALSTOM V4559828-0001
GE P111-6052
ABB 540CMD01
GE IS220PSVOH1A
GE IS220PDIOH1A
GE IS200BAPAH1A
EMERSON 5X00419G02
ABB 3AUA0000110430 BCU-12
BENDER IRDH275B435
GE IS230PCAAH1B
GE IS220PAICH1B
GE IS220YDOAS1A
GEA 0005-4050-430
Rolls-royce R10I53S-MRP1TR01.5
Hirschmann RS20-0800M4M4SDBEHH
Hirschmann RS30-0802OOZZSDAEHH
Hirschmann MS20-1600SABEHH
Hirschmann MM20-T1T1T1T1SBHH
Hirschmann MM20-Z6Z6Z6Z6SBHH
TRICONEX 3721

other

points

PS1

PS2

Figure 17

Test OFF Relays

(opto-isolated)

to

other

points

to other

points &

sensors

Threshold Detect

Opto-Isolator

Simplified Schematic of a 3564 DI Module with a 9566-710 Panel

9566-810 (24 VDC, commoned, 32 pts.)

A

B

C

Termination panel 9566–810 is compatible with 24/48 VDC digital input modules and has 32

input points and commoned power terminals (PWR+ and PWR–). Each input point is protected

by a 180 ohm current-limiting resistor. You should use term panel 9566-810 in 24 volt

applications.

The modules compatible with 9566–810 have 64 points, which means you must use two term

panels for each digital input module.

Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply

the labels, see Appendix F, Panel Labels.

Specifications

This table describes specifications for 9566–810.

Table 32

Specifications for Term Panel 9566–810

Feature

Description

Panel type

Commoned

Points

32