Eaton

Eaton MP-3000 Motor Protection Relay

The MP-3000 is an advanced microprocessor-based motor protection

relay that is easy to set up and use.  It monitors, controls, and protects

motors against overload, thermal damage to rotor or stator, electrical

faults, and excessive starting, and many process equipment failures.

Advanced algorithms and thermal models give safe operation over a

wide range of conditions.

The MP-3000 protects 50 or 60 Hz three-phase motors of any size

or voltage level.  It can protect induction or synchronous motors, with

or without RTDs.  The relay is frequently installed in motor starters or

switchgear.

The MP-3000 Motor Protection Relay provides the following pro

tection, alarm, and control functions.  ANSI device numbers are in

parentheses.

Protection

Intel-I-Trip I2t Overload Protection (49/51)

Locked-rotor protection (49S/51)

Ultimate trip current (51)

Negative sequence current/phase unbalance and reverse

phase protection (46)

Instantaneous overcurrent trip (50)

Ground fault protection (50G)

RTD trip with accessory URTD module (49/38)

Underload trip power and current (37)

Starts per time limit (66)

Jam or stall trip (51R)

Zero-speed switch trip (14)

I2t Auto or manual reset (86)

Fail-safe or non-fail-safe trip modes

alarming

Ground fault

I2t Overload

Jam / Stall

Underload

Eaton MP-3000 Motor Protection Relay

Phase unbalance

RTD temperature with URTD module

Control    features

Transition control for reduced voltage starters

Incomplete sequence (process feedback) detection and trip

Permits user-set number of cold starts

Limits number of starts per time

User sets minimum time between starts

Antibackspin (time from stop to next start) delay

Current-based process load shedding and restoration

Long acceleration timing feature

Motor stop input for synchronous motor and condenser

applications

Remote trip input

Differential trip input

Emergency override clears blocks to motor restarting (if

enabled)

Program settings while motor runs, with controlled change

over (if enabled)

Disarmed mode for commissioning and checking in a

running process

MP-3000 features and Enhancements

The MP-3000 Motor Protection Relay incorporates the field proven

motor thermal models and sequence component measurement

techniques that were pioneered in the IQ 1000 II relay thermal models.

The MP-3000 also adds several enhancements. Significant enhance

ments and features include:

1. Recognized to meet UL 1053 Standards for Ground Fault Protec

tion Devices.

2. Power supply operates continuously at 55% of nominal supply

voltage.  It can ride through a voltage sag or loss for 30 cycles

without dropping out and taking the motor off line.

3. Optional Quick Release Drawout Case that makes removal and

replacement fast and easy.

4. New Armed/Disarmed feature for trip-free installation with Quick

Release Drawout Case.

5. User selectable trip or alarm only on relay internal failure detec

tion.

6. Real-time clock for date and time stamping of trips, alarms, and

events (Y2K compliant).

7. Expanded memory for extensive recording and logging of events,

trips, alarms, history, and motor starting current profiles.

8. Motor starting profile plot versus protection limits.

9. Easy-to-use faceplate and user interface.  Settings and data are

organized into pages under six main modes.  The modes are

Default (motor state), Monitor, View Setting, History, Logs, and

Program (change settings).

10. intel-i-trip Intelligent Overload Protection with adaptive trip char

acteristics based on RTD readings and motor operating history.

11. RTD diagnostics and communications error checking for addi

tional security against operation from RTD failures.

12. Mechanical Process Load Shedding feature provides overload

indication to control upstream processes, averting unnecessary

motor overload shutdown or jam trips, and maintaining process

continuity