Eaton 9465-ET-M-ST IS Media Converter Multimode
MTL9465-ET
10/100Mb Media Converter
FEATURES
♦ Intrinsically Safe ATEX / IECEx certified, FM / FMC approved
♦ Ga Ex ia IIC T4 GD (surface), Ma Ex ia I M1 (mining)
♦ Zone 1/ Division 1 mounting in a suitable enclosure
♦ Input voltage: 12V dc (10 – 15.4V)
♦ Input current: 160mA
♦ Extended temperature range (–20°C…+70°C)
♦ PoEx™ – “Power over Ethernet” powered device option – accepts module supply via the Cat5e cable*
♦ 10/100Mb Ethernet twisted pair (Cat5e) RJ45 Connection (100m max)
♦ Fibre Optic connections:
ST style 62.5/125mm Multimode (9465-ET-M-ST)
SC style 62.5/125mm Multimode (9465-ET-M-SC)
SC style 9mm Single-mode (9465-ET-S-SC)
♦ Extended distance through the use of 1300nm optics – Typically:
5Km @ 10Mbps over 62.5/125 fibre cable 2Km @ 100Mbps over 62.5/125 fibre cable
♦ Status LED’s For:
‘Power On’
Fibre Optic ‘Link 10Mb’ or ‘Link 100Mb’ Established
Fibre Optic ‘Tx/Rx Activity’
Copper UTP ‘Link 10Mb’ or ‘Link 100Mb’ Established
Copper UTP ‘Tx/Rx Activity’
♦ Transparent operation – 10/100Mbps, Full/Half Duplex with Auto-Negotiation
♦ Supports IEEE 802.3: 10Base-T, 10Base-FL, 100Base-TX and 100Base-FX/SX
♦ DIN-rail mounting module
DC power input
Note: An alternative is to supply the power via the Cat5e cable to the RJ45 connector (PoEx)
Terminal No .
+12V dc in
+12V dc in
0V
0V
5 – 8
Note:
No connection
| UniOP | eTOP40B-0050 |
| ABB | PM866AK02 3BSE081637R1 |
| SARTORIUS | MDB-8E |
| ROLLS-ROYCE | SLIO 02 |
| Bently Nevada | 3500/22M-01-01-01 |
| Alstom | UT150-2 |
| EMERSON | PR6423 009-041+CON 041/913-030 |
| Honeywell | HCIX15-TE-FA-NC |
| KEBA | D3-DU 360/A-2100-20 |
| SARTORIUS | MDB-8E |
| ALSTOM | ALSPA CE 80-20 |
| ALSTOM | Test PLUG MMLB01 |
| Rolls-Royce | ACP-04S19-002 |
| ABB | REM545BG227AAAB |
| EPRO | PR9376/010-011+CON021 |
| Rolls-Royce – | ACP-04S12-001 20095201 |
| ABB | RET 670*2.0-A40X00 Order = 4202183240-130 Ordering no: 1MRK004816-CE |
1. (Terminals 1+2. 3+4 linked internally)
3 .3 .2 Front Panel Connectors
10/100 BASE-T Ethernet RJ45
Pin No .
Function
RX +
RX
TX +
Supply 12V – PoEx
When using PoEx – no
supply is required on these
terminals.
Supply 12V – PoEx
TX –
Supply 0V – PoEx
8
Supply 0V – PoEx
When using PoEx – no
supply is required on
screw terminals 1 to 4 – see
above.
When connecting the Cat5e cable to a 9466 Ethernet switch, or other device that supports Auto
MDI/MDI-X, a straight connected RJ45 cable is used, a cross-over cable is only required if the other
device does not support this auto detect mode.
It is recommended that Cat5e cables for Hazardous Area Zone 1 use are ‘Blue’ in colour and are
of good quality (see accessories section), the Safe Area cables being a colour other than blue to
aid identification.
10/100 BASE-FL ST(or SC) – Fibre Optic
The fibre optic cable is connected to the ST (or SC) style ports on the front panel, the top one of
which is transmit (TX), the lower one receive (RX). When connecting fibre cable between a pair
of media converters a cross-over is required – i.e: TX on one module connects to RX on the other
module