Honeywell

Honeywell X-DCS2000/EN Digital Integrated System Manager 50/60Hz 100-240V #4

X-DCS2000/EN

DIGITAL INTEGRATED

SYSTEM MANAGER

• Highly integrated

• Easy-access preset buttons

• Built-in fault diagnosis

• Automatic volume control

• Extendable zones connections via software

configuration

DESCRIPTION

X-DCS2000/EN

X-DCS2000/EN Digital Integrated System Manager (abbr.

DCS) is the basic unit of X-618 Public Address and Voice

Alarm System. DCS integrates plentiful functions such as

zone expansion, multiple audio sources support, audio file

FEATURES

Input/ Output

DCS has 8 dry-contact outputs that can

be used to activate external devices. It

has 8 pairs of loudspeaker line output

where each one allows multiple 100V

loudspeakers to

be connected in parallel. A record output

port is dedicated for external recording.

DCS also has 8 dry-contact inputs that

can be linked with a fire alarm control

center which supports broadcasting

alarm tones and evac- uation

announcement when fire happens. On

the rear panel, there are 4 network audio

input and 4 auxiliary inputs, which

provide con- nections to external audio

sources such as CD/DVD, cassette, FM

tun- er etc. In addition, there are 4 audio

inputs that are capable to adjust volume

automatically according to ambient

noise (when HN-D32N Noise Detector is

installed). Users can set the phantom

power and

storage, net audio, broadcasting, zone control, monitoring,

fault diagnosis etc. The supplied X-SMART management

software allows users to easily and efficiently manage and

control the system.

input gain of each volume control input

on the rear panel.

Connections Expansion

DCS can connect with devices and the

network to extend zone connections via

4 10M/100M adaptable Ethernet

interfaces.​

Safety and Robustness

DCS can detect errors on main power

supply, backup power supply, amplifier

circuit, amplifier protection, software,

communications, and loudspeaker line

in runtime. By locating the error’s

occurrence, DCS provides valuable

information for repairing or replacing

the malfunctioned devices.

DCS supports power supply and

amplifier redundancy. Built-in fuse

provides over-current protection

to the main power supply. When

a shortcircuit error is detected in DCS,

the power supplied from main power will

be cut off and switched to the backup

one. Same technology is also used in

amplifier switchover. User can configure

the amplifier backup solution as 3

backup for 1 main, 2 backup for 1 main,

1 backup for 1 main or 2 backup for 2

main.

Audio Storage

DCS is built with a 1GB flash memory.

Via X-618 Config software, users can

upload audio files for later playback or

audio synthesis. Volume controllers can

be connect- ed with the DCS contact

outputs to adjust the zones volume or

force switching

Leave a Reply

Your email address will not be published. Required fields are marked *