Alstom DIN3380220BM Inverter

General Description

The ALSPA MV3000e PROFIBUS Fieldbus Coupler may be

retrofitted to the whole range of ALSPA MV3000e drives and allowVS

the drive to be connected to a PROFIBUS-DP network.

This manual describes the two types of PROFIBUS Fieldbus

Coupler that may be fitted in an ALSPA MV3000e AC drive

MVS3007-4001 supplied up to December 2002 and

MVS3007-4002 supplied after December 2002.

PROFIBUS Configuration

The PROFIBUS board is used as a slave device on a PROFIBUS

link.

The board is parameterised and controlled using the same

parameter interface as the rest of the drive. The board may alsbe

configured over the drive’s serial links, but it is not possible to

configure the board over the PROFIBUS link itself.

GSD File

The GSD file is used to provide a profile of the slave devicce to the

master device on the bus. The files for both ALSPA PROFIBUS

Fieldbus Couplers are provided on a diskette supplied with the

PROFIBUS board.

GE DS200SLCCG1AFG
GE DS200TCEAG1BNE
GE DS200TCEBG1ACE
GE DS200TCPDG1BEC
GE DS200TCPDG2BEC
GE DS200TCRAG1ACC
GE DS200TCTGG1AFF
GE DS200UDSAG1ADE
GE DS2020CMB1206CGDDD8E
GE DS2020PDMAG6
GE DS215DMCBG1AZZ03A

Associated Publications

T1676 – ALSPA MV3000e Getting Started Manual

T1679 – ALSPA MV3000e Software Technical Manual

T1689 – ALSPA MV DELTA (Air Cooled) Technical Manual

T1693 – ALSPA MV DELTA (Liquid Cooled) Technical Manual

PROFIBUS Board Specification

Fieldbus

Capable of communication rates from 9600 bit/s to 12Mbit/s (1.5M

bits/s for MVS3007-4001 PROFIBUS board).

Automatic Baud rate’ selection from the following list:

9.600 bits/s

19.200 bits/s

93.750bits/s

187.500 bits/s

500K bits/s

1.5Mbits/s

3M bits/s (MVS3007-4002 PROFIBUS board only)

6M bits/s (MVS3007-4002 PROFIBUS board only)

12M bits/s (MVS3007-4002 PROFIBUS board only)

PROFIBUS Protocol

Implements the PROFIBUS-DP Fieldbus protocol according to DIN

19245.

Data Refresh Rate

Data is exchanged between the PROFIBUS Fieldbus module and

the drive’s parameters every 10ms.

MVS3007-4001 board Data Volume

Cyclic Channel Receive:

1 control word (16 bit), and

5 reference demands (16 bit),

or,

2 control words (16 bit), and

4 reference demands. (16 bit).