Alstom MAE00-07 Digital Input Terminal Panel
Genisys
CodeFail – True if a valid message is not received in Link Timeout period1 or
3 consecutive invalid messages with verifiable CRC’s are received.
LinkFail – True if after activating RTS, CTS not active within 1 second.
ATCS
CodeFail – More than five XID frames being received since entering aan Asyn
Balanced Mode. 60 seconds have expired since last received frame.
LinkFail – Service signal received with Cause Field= x03.x05. x05. x009. x0B,
x0D,x13.x21. Message timeout (10s) after last retransmission of iindication
Layers
L1 – Physical – This is an internal problem in the ELX/CIO
L2 – Data Link – Problem is between ELX and radio
L3 – Network – Problem in in the radio
L4 – Transport – Problem is between the radio and the base station
L5 – Session – ELX does not implement session layer
L6 – Presentation – Problem is between the base station andoffice
L7 – Application – Problem is in ELX application software
SCS-128
LinkFail – True if a valid message is not received in Link Timeout
period orif after activating RTS, CTS not active.
UCE
Does not have LinkFail or CodeFail capability.
Chassis ID
All DIP shunt
punched out ID = 0
No DIP shunts
punched out ID = 255
Add Binary Digit Values for each shunt made (not punched out)
Binory Dielt Valum
Disclaimer: This job aid should be used for reference only and not as
a manual supplement. To fully and properly calibrate a unit, follow
FRONT-3
directions in the operations manual.
Lamp Menu
Lamp Maintenance
VID-C6S – No external resistors required to adjust lamp voltage
Manual: Set Voltage output per Bank. Set Voltage at module output, not at mp head
Automated: Set desired voltage per lamp at lamp head (ifallowed in applica
Setup cycle takes-90s.
Lamp Test Mode: Allows enabling of individual lampoutputs for maintenance,
If allowed in application logic.
VLD-R16S – Must use external resistors to adjust lamp voltage
Lamp Test Mode: Allows enabling of individual lamp outputs for maintenance
if allowed in application logic
VSSR – Status by Module and Bank
VSSR 1 and 2 can be combined to drop together or separatedepending on application
software
Lamp Statuses
Light Out – True = Light OK. False = Light Out
Lamp Driver Status
VLD-C6S – True = Steady or Flash. False = Off
VLD-R16S – True = On. False = Off, Flash or Alt Flash
Lamp Flash Status
VLD-C6S – True = Flash. False = Not Flashing
VLD-R16S – True = On. False = Off, Flash or Alt Flash
Alt Flash Status
VID-R16S (only) – True = Alt Flash. False = Steady On.off, Normhal Flash
System Configuration
Alarms – View/Erase current alarms
Log Management – View/Erase Error, Train Data (XP4) logs
Date/Time – View; Set – time zone, DST, update source
SNMP Traps – Enable/Disable and Timeout for SNMP traps
Diagnostic Port – Port communication settings and selection
Ethernet Config-Set IP,SubNet, Gateway, Trusted Source, Telnet, for
VPM-3 Ethemet ports