ALSTOM 029.228406 Inverter

Ethernet Executive Upload Procedure (Recommended)

Note: It isrecommended the configuration is saved before proceeding!

Enter Update Mode as described in the Update Mode section

Select ‘Executive/Boot’ from the ‘Upload New’ drop-down, then

browse and select the Executive software file to be uploaded

If the Executive file is successfully uploaded, “File Successfully

Uploaded” will appear in the dialog box

Verify the correct build and CRC information is displayed.

To apply the Executive file, click on “Apply Executive/Boot”

When the Executive file is applied successfully, “File Applied

Successfully”, will be displayed

Activate the Executive by pressing the Activate button and following the

instructions on the Web UI. Once activated, reboot the VPM-3 by either

pressing the Reset button or cycling power on the chassis.

Ethernet Application Flash Upload Procedure

(Recommended)

ABB REX615
ABB 3BHS036290R0001 PA110358
WESTERMO TD-36 (485) 3618-0001
ABB MRW-6420P
Honeywell CC-PWRR01
GE 345-E-P5-G5-H-E-M-N-N-1E-D-H
GE SSF16Y216
GE VMIVME-7807
GE ACC-5595-208
Honeywell FC-PSU-UNI2450U
ABB PP846 3BSE042238R1
ALSTOM AL129A
ALSTOM LC105A-2
ALSTOM LC106-1
CONVERTEAM P111-6052
Metso, ND9106FN
GE IS230JPDGH1B

Note: All Parameters will be defaulted if application is changed!!

If Equipped with CI-2. XCI-2 or UCI-3. the application can be uploadedto flash

Enter Update Mode menu as described in Update Mode Section

Select ‘Application’ from the ‘Upload New’ drop down, then browse

and select the file to be uploaded. Only the b1 and mb1 file can be used

If the Application Program is successfully uploaded, “File Successfully

Uploaded” will appear in the dialog box.

To applytheApplication Program, click on ‘Apply

“File Applied Successfully”, will be displayed when successful

Clck the ‘Reset’ button or cycle power on the ElectroLogIXS

The new application file will now be selectable from the Application

Select menu on the CDU or through the web GUI.

ElectroLogIXS Memory Information

Setup and Configuration information is stored on ELX backplane Executive

version 7.26 (Crossing), 6.38(Interlocking), 8.28 (Combined) and oleder. Any

module can be swapped without losing the Setup and Configuration. Persiste101

Logs are stored on the VPM-3 module in non-volatile Flash memory.Application

equations are stored on the EPROM or can be uploaded to the (X)CI2 or UCI-3

Flash memory. An installed EPROM will override the CI flash. The

(X)CI-2 or UCI-3 can only be used with a VPM-3.