ALSTOM

ALSTOM PS482 Controller Module

Check that the connector pins on the underside of the power converter module are

correctly aligned. Orientate the module so that the matching connectors are in line

and the mounting holes correspond with the two mounting pillars nearest to the

front of the controller. Gently push the connector halves together until the module

sits flat on the mounting pillars.

Secure the power converter module in position with 2 of the screws and washers

removed at instruction (c). The unused screws and washers may be stored in the

other two mounting pillars.

(m)  Remove a blanking panel from the front of the controller, to make space for each

of the Fieldbus module front panels. The blanking panels are secured with two M3

Pozi-pan screws, remove and retain the screws.

(n) Secure the Fieldbus front panel(s) in position using the screws removed at

instruction (m).

ABB NDCU-11
GE IS220PRTDH1A
ABB 3BDH000002R1 PM802F
HARMONIC HA-800A-3C-200
A-B T9110
A-B T9451
ROLLS ROYCE 984664H
GE SR469-P5-HI-A20
EATON MA30/D/2/SI
ABB 2TLJ020070R0500
GE KYPDACGP1
GE DS3800HIOB
GE DS3800NGRD1D1C
ABB AO2040
WOODWARD 5463-787
WOODWARD 5501-429
MOOG D651-129B
ABB HMI REF542 PLUS
ABB REF615 HBFJAEAGAAC1BAA11G

(o) Replace the upper right-hand side cover and power supply assembly.  Secure in

position using the screws removed at instruction (a).

Module Identification

A rotary switch located on the fieldbus module PCB achieves module identification. A

maximum of two fieldbus modules can be installed into a GEM80-500. each identified

in the system by reserved rotary switch position 2 or 3.

The GEM80-500 Fieldbus driver will find the module with the lowest switch position

and use the configuration parameters from Pn to configure this module, this is referred

to as Module #1.  The next module if fitted will use parameters from Pn+16. this

referred to as Module #2 (see section 5.2).

If a single Fieldbus module is fitted, the rotary switch must be set to position 2 (Module

#1).  If two modules are fitted, one rotary switch must be set to positions 2 (Module

#1) and the other to position 3 (Module #2).

If a module is removed, ensure that the remaining module’s rotary switch is set to

position 2 and that the configuration data starting at Pn are suitable for the application.

N.B. If two modules are fitted, setting the rotary switch to the same position will cause

malfunction of both modules. Selecting any position other than 2 or 3 will cause

malfunction of the host processor.

Leave a Reply