FOXBORO

Foxboro A431:A593 P0924TR Analog Input Interface Module

The FBM232canaccess up to 64 devices to read or write data. From the Foxboro

DCScontrol station to which the FBM232 is connected, up to 2000 Distributed Control

Interface (DCI) data connections can be made to read or write data. Supported data

types are determined by the particular driver loaded on the FBM232. which converts

the data to the DCI data types listed below:

• Ananaloginput or output value (integer or IEEE single-precision floating point)

• Asingle digital input or output value

• Multiple (packed) digital input or output values (packed in groups of up to 32

digital points per connection).

Control Block Support

The FBM232offers control block support for the following standard Foxboro DCS

Distributed Control Interface (DCI) block types:

BIN

Binary Input

BINR

Binary Input Redundant

BOUT

Binary Output

IIN

Integer Input

IOUT

Integer Output

PAKIN

Packed Input

PAKOUT

Packed Output

PLSOUT

Pulse Output

RIN

Real Input

RINR

Real Input Redundant

ROUT

Real Output

STRIN

String Input

STROUT

String Output

The DCI blocks are configured just like other Foxboro DCS control blocks. The DCI

blocks address and read/write data from/to the addressed field device.

Thus the FBM232 can access up to 2000 analog I/O values, or up to 64000 digital I/O

values, or a combination of digital and analog values up to the maximum capacity a

user allows within the sizing guidelines of the control processor. The frequency of

access to the FBM232 data by a control station can be as fast as 500 ms. The

performance depends on each device type and the layout of data in the device.

The FBM232collects the required data from the devices, performs the necessary

conversions, and then stores the converted data in its database for incorporation into

the Foxboro DCS plant management functions and operator displays. Data may also

be written out to the individual devices from the Foxboro DCS system.

Fieldbus Communications

The Fieldbus Communications Module (FCM100Et or FCM100E) or the Field Control

Processor (FCP270 or FCP280) interface the redundant 2 Mbps module Fieldbus

used by the FBMs. The FBM232 accepts communication from either path of the

redundant 2 Mbps module Fieldbus- should one path fail or be switched at the system

level, the module continues communication over the active path