FOXBORO

Foxboro P0973LN Differential Pressure Transmitter

TerminationAssembliesandSignalConditioners

ThefollowingtableslisttheTerminationAssembliesandSignalConditioners

supported.Youcanselectthemasrequiredatthetimeoforderingtheenclosure.

Table1-SupportedPhoenixTerminationAssembliesandSignalConditioners

Part PhoenixPart

Number

Description

BaseModule

VIP/S/D25M/BASE1-8/L/C/EX

2906595 VIPERbasemodule

(TerminationAssembly),

screwconnection(p/n

2906595)

• ShippedwithIOA

FEED-THRU/EX

(p/n2906598)

• Replacewiththe

IOAsbelow,as

required

IOAAI/AO/BFI/DS/0.5A/EX 2906599 IOA,analogprotection

withdisconnectsandtest

points

IOADI/DO/BFI/DS/1.0A/EX 2906600 IOA,digitalprotection

withdisconnectsandtest

points

IOAREL24VDO/BFI/3.0A/EX 2910153 IOA,24VDOrelay

IOAREL120VDO/BFI/3.0A/EX 2910154 IOA,120VDOrelay

IOAREL24VDI/BFI/1.0A/EX 2910155 IOA,24VDOrelay

IOAREL120VDI/1.0A/EX 2910157 IOA,120VDIrelay

IOAREL230VDO/BFI/NO/3.0A/EX 2910421 IOA,230VDOrelayNO

contact

IOAREL230VDO/BFI/NC/3.0A/EX 2910422 IOA,230VDOrelayNC

contact

IOAREL230VDI/1.0A/EX 2910423 IOA,230VDIrelay

FunctionalSpecifications

Enclosure SS316Lstainlesssteelfieldenclosure

InputPower(Redundant) SeeCompactPowerSupply-FPS480-24(PSS41H-2C480)

MaximumDissipatedPower 148W

MaximumInputPower 480W

EnclosureOverTemperatureAlarm

Setting

70°C(158°F)

RegulatoryCompliance,Electromagnetic

Compatibility(EMC) • EMCDirective2014/30/EU:

Meets:EN61326-1:2013ClassAEmissionsandIndustrial

ImmunityLevels

ProductSafety • UnderwritersLaboratories(UL)forU.S.andCanada:

UL/UL-ClistedassuitableforuseinUL/UL-ClistedClassI,

GroupsA-D;Division2;Hazardouslocationswheninstalledas

describedinFoxboroDCSI-SeriesIntelligentEnclosures

PlanningandInstallationGuide(B0700GX).

CommunicationscircuitsalsomeettherequirementsforClass2

asdefinedinArticle725oftheNationalElectricalCode(NFPA

No.70)andSection16oftheCanadianElectricalCode(CSA

C22.1).ConditionsforuseareasspecifiedinFoxboroDCSI

SeriesIntelligentEnclosuresPlanningandInstallationGuide

(B0700GX).

• EuropeanLowVoltageDirective2014/35/EUandExplosive

Atmospheres(ATEX)Directive2014/34/EU:

II3GExicecnAnCIICT3Gc

II3DExtcIIICT60°CDc

certifiedwheninstalledasdescribedinFoxboroDCSI-Series

IntelligentEnclosuresPlanningandInstallationGuide

(B0700GX).

RoHSCompliance ComplieswithEuropeanRoHSDirective2011/65/EUwhenFBM232

andFBM233optionsarenotfitted