Triconex

TRICONEX 9566-810F – Power Supply Module, Compact, High-Speed

Dual Digital Output Modules

This table identifies termination products you can use with dual digital output modules.

Table 10

Termination Products for 32-Point Dual Digital Output Modules

Termination Option

24 VDC (3664. 3674)

Standard termination panel, commoned

9662-610

Basic termination panel

9653-610

Nonincendive termination panel

9671-610

Relay panel, commoned

9671-810

Fanned-out cable

9101-010

Note You need two termination panels (or cables) for each 32-point dual digital output

module. Also, you can mix any combination of two termination products listed. For

example, you may use two 9662-610 panels, or one 9653-610 basic panel and one

9101-010 fanned-out cable, and so on.

Relay Output Modules

This table identifies termination products you can use with relay output modules.

Table 11

Termination Products for 32-Point Relay Output Modules

Termination Option

Non-Commoned, Normally Open (3636R, 3636T)

Standard termination panel, non-commoned

9668-110

Basic termination panel, non-commoned

9651-110

Fanned-out cable

9101-010

CONVERTEAM P111-6052
Metso, ND9106FN
GE IS230JPDGH1B
Meggit 200-510-071-113
ABB 306A4576P001
GE 246B9953BMG01
Mentor MP420A4R
KEBA SC102
RELIANCE 45C922
RELIANCE 57C554
ABB HESG324430R11/B
FOXBORO fbm232
A-B IMASO01
A-B IMDSO04
Yokogawa YNT511D-V42/KT
ABB NTAI05
GE SGHA36AT0400
AB TLY-A2540P-HK64AA
Foxboro FCM10Ef P0916CP
Mitsubishi FXDOM01(OMN1)
ABB AINT-14C 68685826
ABB CP-C 24/20.0
metso ND9102HN

Note You need two termination panels (or cables) for each 32-point relay output module.

Also, you can mix any combination of two termination products listed. For example, you

may use two 9668-110 panels, two 9651-110 basic panels, or one 9668-110 panel and one

9651-110 basic panel

Analog Input Modules

This table identifies termination products you can use with analog input modules.

Table 12

Termination Products for 16-Point Analog Input Modules

Termination Option

0–5 VDC or 0–10 VDC (3703E)

Standard termination panel, voltage input

9763-810

Standard termination panel, current input

9762-210 (0–5 V)

9762-410 (0–10 V)

Standard termination panel, current input,

user configurable

9771-210 (0–5 V)

Basic termination panel, voltage input

9753-110

Nonincendive termination panel, current input

9791-610

Nonincendive termination panel, voltage input 9787-110

RG 1.180 Term Panel

9790-610 (4–20 mA, 0–5 V)

9792-610 (4-20 mA, 0-5 V, 48 VDC field)

9795-610 (4–20 mA, 0–10 V)

9783-110 (voltage input)

Fanned-out cable

Contact Triconex for availability of analog fanned

out cables

Leave a Reply