Triconex

Triconex 9662-610F Standard Termination Panel Commoned

Compatible Modules

This table describes digital input modules compatible with BP9228-010.

Table 49

Modules Compatible with BP9228-010

Module Part

Number

Points per

Module

Module Description

3503E

32

24 VAC/VDC, commoned in groups of 8 with self-test

3505E

32

24 VDC, low-threshold, commoned in groups of 8 with self-test

BP9229-010 (24 V, bypass, 32 pts., for 64 pt. modules)

Termination panel BP9229-010 is compatible with 24 VDC digital input modules and has 32

input points.

The panel is 3.5 inches high, 4.0 inches deep, and 19 inches wide (88.9 mm x 101.6 mm x

482.5 mm), and complies with EIA Standard RS-310-C. The cable is keyed to the appropriate

digital input module. P1 connects points 1-32. A 6-terminal barrier strip has terminals for

redundant 24 VDC power with diode ORing provided on the panel. Each screw terminal

accepts either #6 ring-lug terminals, or 24-gauge to 12-gauge (0.2 mm2 to 3.3 mm2) wires.

The modules compatible with BP9229-010 have 64 points, which means you must use two term

panels for each digital input module.

Specifications

This table describes specifications for BP9229-010.

Table 50

Specifications for Term Panel BP9229-010

Feature

Description

Panel type

Bypass

Points

32

Compatible Modules

This table describes digital input modules compatible with BP9229-010.

Table 51

Modules Compatible with BP9229-010

Module Part

Number

Points per

Module

Module Description

3504E

64

24 VDC, commoned

Field Wiring Diagrams

This figure illustrates how to connect a 64-point digital input module and a BP9229-010