Triconex 9662-610F Standard Termination Panel Commoned
Compatible Modules
This table describes digital input modules compatible with BP9228-010.
Table 49
Modules Compatible with BP9228-010
Module Part
Number
Points per
Module
Module Description
3503E
32
24 VAC/VDC, commoned in groups of 8 with self-test
3505E
32
24 VDC, low-threshold, commoned in groups of 8 with self-test
BP9229-010 (24 V, bypass, 32 pts., for 64 pt. modules)
Termination panel BP9229-010 is compatible with 24 VDC digital input modules and has 32
input points.
The panel is 3.5 inches high, 4.0 inches deep, and 19 inches wide (88.9 mm x 101.6 mm x
482.5 mm), and complies with EIA Standard RS-310-C. The cable is keyed to the appropriate
digital input module. P1 connects points 1-32. A 6-terminal barrier strip has terminals for
redundant 24 VDC power with diode ORing provided on the panel. Each screw terminal
accepts either #6 ring-lug terminals, or 24-gauge to 12-gauge (0.2 mm2 to 3.3 mm2) wires.
The modules compatible with BP9229-010 have 64 points, which means you must use two term
panels for each digital input module.
Specifications
This table describes specifications for BP9229-010.
Table 50
Specifications for Term Panel BP9229-010
Feature
Description
Panel type
Bypass
Points
32
Compatible Modules
This table describes digital input modules compatible with BP9229-010.
Table 51
Modules Compatible with BP9229-010
Module Part
Number
Points per
Module
Module Description
3504E
64
24 VDC, commoned
Field Wiring Diagrams
This figure illustrates how to connect a 64-point digital input module and a BP9229-010