Triconex

DI2301 7400208B-020 Triconex DI Baseplate Compact Mounting for Safety Systems

Bypass Term Panels

This section describes bypass term panels, which are available for 32-point and 64-point digital

input modules.

Model numbers of these term panels are:

• BP9228-010 (24 V, bypass, 32 pts., for 32 pt. modules)

• BP9229-010 (24 V, bypass, 32 pts., for 64 pt. modules)

This figure represents a typical 32-point bypass termination panel that is compatible with

32-point digital input modules.

Compatible Modules

This table describes pulse input and pulse totalizer input modules compatible with 9753–110.

Table 47

Modules Compatible with 9753–110

Module Part

Number

Points per

Module

Module Description

3510

8

20 Hz to 20 KHz pulse input, non-commoned, AC-coupled, 50 ms

typical input update rate

3511

8

20 Hz to 20 KHz pulse input, non-commoned, AC-coupled, 25 ms

typical input update rate

3515

32

0 to 1 kHz pulse totalizer input, non-commoned

BP9228-010 (24 V, bypass, 32 pts., for 32 pt. modules)

Termination panel BP9228-010 is compatible with 24 VAC/VDC and 24 VDC digital input

modules, has 32 input points, and is supplied with two interface cables.

The panel is 3.5 inches high, 4.0 inches deep, and 19 inches wide (88.9 mm x 101.6 mm x 482.5

mm) and complies with EIA Standard RS-310-C. Each cable is keyed to the appropriate digital

input module. P1 connects points 1-16. and P2 connects points 17-32. A 6-terminal barrier strip

has terminals for redundant 24 VDC power with diode ORing provided on the panel. Each

screw terminal accepts either #6 ring-lug terminals, or 24-gauge to 12-gauge (0.2 mm2 to

3.3 mm2) wires.

Specifications

This table describes specifications for BP9228-010.

Table 48

Specifications for Term Panel BP9228-010

Feature

Description

Panel type

Points

Bypass

32