Triconex

TRICONEX PM6301A analog output module

Basic Digital Input Term Panels

This section describes basic digital input term panels, which are available in 16-point and 32

point configurations.

Model numbers of these term panels are:

• 9551-110 (115 V, basic, 16 pts.)

• 9552-610 (48 V, basic, 16 pts.)

• 9553-610 (24 V, basic, 16/32 pts.)

• 9750-310 (24 VDC, basic, 32 pts.)

• 9750-410 (48 VDC, basic, 32 pts.)

This figure represents a typical 16-point or 32-point basic digital input termination panel.

J1

TRICONEX   TM

DIDO PANEL

7400143-

Typical 16-Point/32-Point Basic DI Term Panel

9551-110 (115 V, basic, 16 pts.)

Termination panel 9551–110 is compatible with 115 VAC/VDC digital input modules and has

16 input points.

The modules compatible with 9551–110 have 32 points, which means you must use two term

panels for each digital input module.

Specifications

This table describes specifications for 9551–110.

Table 36

Specifications for Term Panel 9551–110

Feature

Description

Panel type

Basic

Points

16

Compatible Modules

This table describes digital input modules compatible with 9551–110.

Table 37

Modules Compatible with 9551–110

Module Part

Number

Points per

Module

Module Description

3501E

32

115 VAC/VDC, non-commoned, isolated, TMR

3501T

32

Field Wiring Diagrams

115 VAC/VDC, non-commoned, isolated, TMR

This figure illustrates how to connect a 32-point digital input module and a 9551–110 to the field.

Simplified Schematics

This is a simplified schematic of a typical 32-point digital input module without self-test and a

9551–110 (1 of 32 module points shown).

9552-610 (48 V, basic, 16 pts.)

Termination panel 9552–610 is compatible with 48 VAC/VDC digital input modules and has 16

input points.

The modules compatible with 9552–610 have 32 points, which means you must use two term

panels for each digital input module.

Specifications

This table describes specifications for 9552–610.

Table 38

Specifications for Term Panel 9552–610

Feature

Description

Panel type

Basic

Points

16