Triconex

TRICONEX 9662-1 terminal block

Specifications

This table describes specifications for 9563-910.

Table 26

Specifications for Term Panel 9563-910

Feature

Description

Panel type

Commoned, resistor protected

Points

16

Compatible Modules

This table describes digital input modules compatible with 9563-910.

Table 27

Modules Compatible with 9563-910

Module Part

Number

Points per

Module

Module Description

3503E

3505E

32

32

FOXBORO RH914TR
FOXBORO P0926GU
YOKOGAWA SCP451-11
Honeywell UT762AGA/Z
Honeywell S0854485
Honeywell S0815344
Honeywell S0854962
ABB ACS880 ZCU-14
GE AT868-2-1-1
Honeywell FE-USI-0002
MOOG G771K202A
ABB 07AC91 GJR5252300R0101
Foxboro RH101AB
Foxboro 4000189-530
ABB DHH810-MFT
GE MLJ1005B010F00C
ALSTOM 029.359 325
WOODWARD E8250-502
GE SR489-P5-HI-A20
ABB 3BHL000391P0101

24 VAC/VDC, commoned in groups of 8. TMR with self-test

24 VDC, low-threshold, commoned in groups of 8. TMR with self-test

Field Wiring Diagrams

This figure illustrates how to connect a 32-point digital input module and a 9563-910 to the field.

Simplified Schematics

This is a simplified schematic of a typical 32-point commoned digital input module with self

test (1 of 32 module points shown)

32-Point Commoned Digital Input Term Panels

This section describes 32-point commoned digital input term panels, which are available with

fuses and blown fuse indicators or resistors for field device protection. Model numbers of these

term panels are:

• 9565-810 (48 VDC, commoned, 32 pts.) (fuse protection)

• 9566-710 (24 VDC, commoned, 32 pts.) (resistor protection)

• 9566-810 (24 VDC, commoned, 32 pts.) (resistor protection)

This figure represents a typical 32-point commoned digital input term panel that has fuses and

blown-fuse indicators for field device protection.

9565-810 (48 VDC, commoned, 32 pts.)

Termination panel 9565–810 is compatible with 24/48 volt DC digital input modules and has 32

input points and commoned power terminals (PWR+ and PWR–). Each input point is protected

by a fuse with a blown-fuse indicator. You should use term panel 9565-810 in 48 volt

applications.

The modules compatible with 9565–810 have 64 points, which means you must use two term

panels for each digital input module.

Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply

the labels, see Appendix F, Panel Labels.

Specifications

This table describes specifications for 9565–810.

Table 28

Specifications for Term Panel 9565–810

Feature

Description

Panel type

Commoned

Points

32

Leakage current per point

Maximum: 3.5 mA

Typical: 2.0 mA

Compatible Modules

This table describes digital input modules compatible with 9565–810.

Table 29

Modules Compatible with 9565–810

Module Part

Number

Points per

Module

Module Description

Fuse

3504E

64

24/48 VDC, commoned, high-density, DC-coupled,

TMR

Leave a Reply