TRICONEX JWA600-24 Digital Input Module
9563-810 (24 V, commoned, 16 pts.)
Termination panel 9563–810 is compatible with 24 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
fuse with a blown-fuse indicator.
The modules compatible with 9563–810 have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.
Specifications
This table describes specifications for 9563–810.
Table 24
Specifications for Term Panel 9563–810
Feature
Description
Panel type
Commoned
Points
16
Leakage current per point
Maximum: 3.3 mA
Typical: 2.5 mA
Compatible Modules
This table describes digital input modules compatible with 9563–810.
Table 25
Modules Compatible with 9563–810
Module Part
Number
Points per
Module
Module Description
Fuse
3503E
3505E
32
32
24 VAC/VDC, commoned in groups of 8. TMR with
self-test
24 VDC, low-threshold, commoned in groups of 8
with self test, TMR
1A, slow
1A, slow
9563-910 (24 V, commoned, resistor protected, 16 pts.)
Termination panel 9563-910 is compatible with 24 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
180 ohm resistor.
The modules compatible with 9563-910 have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels