Triconex 4352AN Tricon Communication Module
HART Interface Modules
This table identifies termination products you can use with HART AI and AO interface
modules.
Table 19
Termination Products for HART Interface Modules
Termination Option
HART AI Interface
(2770H)
HART AO Interface
(2870H)
Standard termination panel, current input
9761-210
n/a
Basic termination panel
n/a
9853-610
Nonincendive termination panel
9791-610
9861-610
RG 1.180 termination panel
9790-610
9860-610
Installing a Termination Panel
This procedure explains how to install a termination panel.
Procedure
1 Set up the Tricon chassis and install the I/O modules as described in the Planning and
Installation Guide for Tricon v9–v10 Systems.
2 Remove incoming power from the Tricon system (optional).
3 Mount the termination panel on a DIN rail as shown in these pictures.
Note These termination panels cannot be installed on a DIN rail. They must be
installed on a standard 19 inch (47.5 cm) rack (Electronics Industries Association
Standard #RS-310-C):
• 9251-210
• 9670-110
• 9670-610
• 9671-810
• 9672-810
• 9673-810
Attach one end of the interface cable to the ELCO connector on the termination panel.
• Ensure that the mating surfaces of the ELCO connectors on the cable and the
termination panel do not have any bent pins or other damage, and that both male
and female keys match.
• Position the connector on the cable so that it is aligned with the connector on the
termination panel.
Ensure that the
male and female
keys match.
• Mate the two connectors together until the threaded end of the thumbscrew is
making contact with the nut in the female connector. You may need to slightly rock
the connector on the cable while mating it to the connector on the termination
panel.
• As you apply pressure to the top of the connector on the cable, use your other hand
to turn the thumbscrew clockwise until the connectors are mated completely. The
minimum torque requirement is 8.85 lbf in (10.0 d-Nm).