Triconex

TRICONEX 4000093-316 communication module

Supervised Digital Output Modules

This table identifies termination products you can use with 8-point supervised digital output

modules. You can use only one of the terminations listed in a particular module’s column.

Table 7

Termination Products for 8-Point Supervised Digital Output Modules

Termination Option

115 VAC

(3611E)

120 VDC

(3613E)

24 VDC

(3614E)

24 VDC (low power)

(3615E)

48 VDC

(3617E)

Standard termination

panel, commoned

9661-510

9661-810

9662-910

9662-710

9667-910

Note You need one termination panel (or cable) for each 8-point or 16-point supervised DO

module.

Table 8

Termination Products for 16-Point Supervised Digital Output Modules

Termination Option

120 VDC (3623)

120 VDC (3623T)

24 VDC (3624)

Standard termination panel,

commoned

9661-910

9664-810

9662-610

Basic termination panel

9651-110

9651-110

9653-610

Nonincendive termination panel n/a

n/a

9671-610

Fanned-out cable

9101-010

n/a

9101-010

Supervised/Non-Supervised Digital Output Modules

This table identifies termination products you can use with 32-point supervised/non

supervised digital output modules.

Table 9

Termination Products for 32-Point Supervised/Non-Supervised Digital Output

Modules

Termination Option

24 VDC (3625)

Standard termination panel, commoned

9662-610

Basic termination panel

9653-610

Nonincendive termination panel

9671-610

Fanned-out cable

9101-010

Note You need two termination panels (or cables) for each 32-point digital output module.

Also, you can mix any combination of two termination products listed. For example, you

may use two 9662-610 panels, or one 9653-610 basic panel and one 9101-010 fanned-out

cable, and so on

Dual Digital Output Modules

This table identifies termination products you can use with dual digital output modules.

Table 10

Termination Products for 32-Point Dual Digital Output Modules

Termination Option

24 VDC (3664. 3674)

Standard termination panel, commoned

9662-610

Basic termination panel

9653-610

Nonincendive termination panel

9671-610

Relay panel, commoned

9671-810

Fanned-out cable

9101-010

Note You need two termination panels (or cables) for each 32-point dual digital output

module. Also, you can mix any combination of two termination products listed. For

example, you may use two 9662-610 panels, or one 9653-610 basic panel and one

9101-010 fanned-out cable, and so on.

Relay Output Modules

This table identifies termination products you can use with relay output modules.

Table 11

Termination Products for 32-Point Relay Output Modules

Termination Option

Non-Commoned, Normally Open (3636R, 3636T)

Standard termination panel, non-commoned

9668-110

Basic termination panel, non-commoned

9651-110

Fanned-out cable

9101-010

Note You need two termination panels (or cables) for each 32-point relay output module.

Also, you can mix any combination of two termination products listed. For example, you

may use two 9668-110 panels, two 9651-110 basic panels, or one 9668-110 panel and one

9651-110 basic panel

Leave a Reply