Eaton T100H-2500-5HC PWR SUPPRESS T100 HW
Eaton T100H-2500-5HC PWR SUPPRESS T100 HW 2.5KVA, 50 HZ, 55DEG C MAX
Eaton’s Power-Suppress 600 is designed with two full-length
electrostatic shields that provide 126 dB common mode noise
attenuation. An optional third shield is available that increases
the attenuation to 146 dB, 20 dB additional attenuation. The
Power-Suppress 600 not only attenuates noise from input to
output, but also prohibits system backfeed from noise-generating
loads. In addition, an optional pre-wired, high-frequency filter
and category C3 surge protection device (SPD) provide your
critical loads with optimum protection from noise and impulses,
as well as high-energy voltage transients.
The Power-Suppress 600’s noise attenuation is critical for any
application in which digital circuitry is used to scan, measure or
monitor critical data, control a critical process, or reproduce high
quality audio/video signals.
Optional infrared, transparent polymer IR window provides access
for safe routine thermal scanning of transformer connections under
load, without exposing personnel to arc flash hazards. Durable IR
windows are industrial-grade with a patented reinforced grill, fully
impact-resistant, and ULT and cULT Listed. This option adds 2 inches
to the depth of the 112 kVA – 225 kVA enclosure.
Specifications
Description Specification
Three-phase power output
kVA 15. 30. 45. 75. 112. 150. 225. 300. 500
Operating frequency
Frequency 60 Hz ± 5%
Note: 50 Hz models available, consult factory.
Electrical input
Three-phase
15–150 kVA
225–500 kVA

208. 240. 480 or 600 Vac (delta)
480. 600 Vac (delta)
Voltage taps (15–300 kVA A) (2) taps 2.5% full capacity above nominal
(4) taps 2.5% full capacity below nominal
500 kVA (1) tap 3.5% full capacity above nominal
(2) taps 3.5% full capacity below nominal
Note: Special voltages available for both
single- and three-phase models.
Electrical output
Three-phase 208/120. 480/277 or 600/347 Vac (wye)
Note: Special voltages available; contact factory.
Output impedance 2% to 3.5% typical
Output distortion Less than 1.0% THD added under linear load
Load regulation 2% typical, no load to full load
Overload Up to 500% for 10 seconds, 1000% for 1 cycle
Isolated neutral Establishes a new neutral to ground bond on the
transformer’s output
Noise attenuation
Common mode 126 dB—standard double (2) shield
146 dB—optional triple (3) shield
Transverse mode 3 dB down at 10 kHz, decaying 20 dB per decade;
decaying 40 dB with “SPD with high frequency” option
Environmental
Operating ambient
temperature–25 °C to +40 °C
Relative humidity 0 to 95% noncondensing
Altitude Up to 5000 feet above sea level without derating
Audible noise 45 to 55 dBA at 1 m, depending on kVA size
Efficiency
U.S. Meets and exceeds U.S. Department of Energy (DOE)
2016 high-efficiency standards identified under DOE
10 CFR Part 431
Canada Meets and exceeds CSAT Standard C802.2-12
K-factor ratings
Ratings K13
Neutral size Twice the ampacity of the secondary phase conductor
on three-phase models