During normal operation, the ConnectUPS Card controls the
communication path to the UPS and allows network-based access to
UPS data through the Web and SNMP. Some situations require direct
serial communication to the UPS in a pass-through mode, such as:
The UPS firmware requires a field upgrade with a 9600 baud serial
port connection to the UPS.
The user wants to run a local copy of LanSafe software with serial
communication to the UPS.
The card’s Normal mode of operation must be disabled for Serial
Pass-Through mode to be available.
Reconfiguring the Card for Serial Pass-Through Mode
NOTE In Serial Pass-Through mode, communication through the ConnectUPS Card Ethernet
port stops, and any existing connections (such as to NetWatch software clients or SNMP
management tools) cease. However, the Ethernet switch functionality of the ConnectUPS
Card continues to function.
The following steps disable Normal mode by changing the switches on
the ConnectUPS Card and restarting the card in Serial Pass-Through
mode.
MITSUBISHI ENGINE OPERATOR CONTROL CIRCUIT NF400-SEW 400AMPS
Telemechanics TSXT3170 Terminal T317 connects only T317 terminal line
Festo CMMP-AS-C5-3A 550042
ABB AX411/11104
SCHNEIDER ELECTRIC OTB1E0DM9LP Ethernet TCP/IP
Schneider Electric STBNIP2311
Siemens 6AU1432-2AA00-0AA0
SIEMENS 6SL3224-0BE22-2AA0
ALLEN-BRADLEY 22B-A5P0N104
Atlas Copco D313-DL-ADVANCED
Contraves Varidyn Compact ADB/V190.45 Servo Controller 13KVA GB402.878-V
KIMO MotorMaster MM 2.2FMC-emc
GRUNDFOS – SCAN MESSTECHNIC D-320-GF1-230 / DID-1 TI1-CND
QGEORGIN REGULATOR DFML10B
Kl枚ckner Moeller | Compact Automation Device | PS3-DC-EE
KEB 10.F0.220-3429 4.0KVA 2.2KW
KEB Combivert 11.F0.R11-3429 94352753/106824 5.2KVA 3KW
PR1555 Philips PR1555/00 Digital Weight Display Board
PR1628 Philips PR1628/60 Control Panel
IKUSI TM70/2.21
Siemens Contactor 3TF52 3TF5222-0AF0
770-500-002 MECMAN IPC 500S PROGRAM LOADER 4K INDUSTRIAL PROGRAMMABLE CONTROLLER
KIMO ELECTRIC 11S2-27
KIMO SCM1-12 Safety Control Module 1
ABB 1SCA022753R3800 OS400D12
To reconfigure the card for Serial Pass-Through mode:
1. Note the current position of DIP switches on the card [the default
setting for both switches is the 0 (off) position]. Write them here for
later reference.
DIP Switch 1 _____ 0 (off) _____ 1 (on)
DIP Switch 2 _____ 0 (off) _____ 1 (on)
2. Set both DIP switches to the 1 (on) position for Serial Pass-Through
mode
Using a pen or paperclip, press the RESET switch on the card to
restart the card in the Serial Pass-Through mode.
4. Locate the configuration cable (labeled “PC”) that was supplied
with the ConnectUPS Card.
5. Plug the RJ-45 end of the configuration cable into the COM port on
the card.
Verify that you have used the port labeled “COM.” The other ports
on the card will not work for configuration.
6. Plug the other end of the configuration cable into the serial COM
port on the computer.
7. Set up the PC to communicate with the UPS serially:
Open your terminal emulation program (such as HyperTerminal®).
Select the appropriate serial connection (such as COM1).
Set the serial line to 9600 baud, No parity, 8 data bits, 1 stop bit,
and no flow control.
Returning the Card to Normal Operation
After using the card in Serial Pass-Through mode, restart the card in
Normal mode:
1. Disconnect the configuration cable from the card and PC.
2. Return the card’s switches to the original settings noted in Step 1
on page 32.
3. Using a pen or paperclip, press the RESET switch on the
ConnectUPS Card to restart the card in Normal mode.