Basler Electric

Basler Electric GENERATOR PROTECTION SYSTEM BE1-GPS100

INSTRUCTION MANUAL

FOR

GENERATOR PROTECTION SYSTEM

BE1-GPS100

The BE1-GPS100 Generator Protection System is an economical, microprocessor based, multifunction

system that is available in a drawout, H1 (half-rack), S1. and S1 double-ended package. BE1-GPS100

relays provide a comprehensive mix of protective functions to detect generator faults and abnormal

operating conditions in an integrated system. This system is suitable for any generator application and

many utility/co-generation facility Intertie applications. BE1-GPS100 features include:

• Three-phase and Neutral Overcurrent Protection

• Negative Sequence Overcurrent Protection

• Undervoltage and Overvoltage Protection

• Negative Sequence Overvoltage Protection

• Frequency Protection

• Directional Power Protection

• Volts per Hertz Protection

• Loss of Field Protection

• Breaker Failure Protection

• Synchronism Checking

• VT Circuit Monitoring

• Virtual Selector Switches

• General Purpose Timers

• Real-Time Instrumentation

• Reporting Functions

• Communication

• Self Diagnostics

• Logic Programmable (BESTlogic™)

BE1-GPS100 relays have four programmable contact sensing inputs, five programmable outputs, and

one alarm output. Outputs can be assigned to perform protection, control, or indicator operations through

logical programming. For example, protection functions could be programmed to cause a protective trip.

Control functions could be programmed to cause a manual trip, manual close, or automatic reclose.

Indicators could be configured to annunciate relay failure, a settings group change, and others.

Protection scheme designers may select from a number of pre-programmed logic schemes that perform

the most common protection and control requirements. Alternately, a custom scheme can be created

using BESTlogic.

A simplified Getting Started procedure for BE1-GPS100 users is provided in Section 2. Quick Start.

Features

The BE1-GPS100 relay includes many features for the protection, monitoring, and control of power

system equipment. These features include protection and control functions, metering functions, and

reporting and alarm functions. A highly flexible programmable logic system called BESTlogic allows the

user to apply the available functions with complete flexibility and customize the system to meet the

requirements of the protected power system. Programmable I/O, extensive communication features, and

an advanced HMI (human-machine interface) provide easy access to the features provided.

The following information summarizes the capabilities of this multifunction device. Each feature, along

with how to set it up and how to use its outputs is described in complete detail in the later sections of this

manual.

Input and Output Functions

Input functions consist of Power System Measurement and Contact Sensing Inputs. Programmable

Contact Outputs make up the output functions. Input and Output functions are described in the following

paragraphs.

Power System Measurement Functions

Three-phase currents and voltages are digitally sampled and the fundamental is extracted using a

Discrete Fourier Transform (DFT) algorithm. Digital sampling of the measured frequency provides high

accuracy at off-nominal values.

The voltage sensing circuits automatically configure themselves internally for single-phase, three wire or

four wire voltage transformer circuits. Voltage sensing circuitry provides voltage protection, frequency

protection, and watt/var metering. Neutral (residual) and negative sequence voltage magnitudes are

derived from the three-phase voltages. An auxiliary voltage sensing input provides protection capabilities

for over/undervoltage monitoring of the first and third harmonic of the VT source connected to the Vx

input. This capability is useful for stator ground fault protection and sync-check functions.

Each current sensing circuit is low burden and isolated. Neutral (residual) and negative sequence current

magnitudes are derived from the three-phase currents. An optional independent ground current input is

available for direct measurement of the current in a transformer neutral, tertiary winding, or flux balancing

current transformer.

Contact Sensing Inputs

Four programmable contact sensing inputs (IN1. IN2. IN3. and IN4) with programmable signal

conditioning provide a binary logic interface to the protection and control system. Each input function and

label is programmable using BESTlogic. A user-meaningful label can be assigned to each input and to

each state (energized and de-energized) for use in reporting functions.

Contact Outputs

Five programmable general-purpose contact outputs (OUT1. OUT2. OUT3. OUT4. and OUT5) provide a

binary logic interface to the protection and control system. One programmable, fail-safe contact output

(OUTA) provides an alarm output. Each output function and label is programmable using BESTlogic. A

user-meaningful name can be assigned to each output and to each state (open and closed) for use in

reporting functions. Output logic can be overridden to open, close, or pulse each output contact for testing

or control purposes. All output contacts are trip rated.

Protection and Control Functions

Protection functions consist of Overcurrent, Voltage, Frequency, Power, Fuse Loss, Breaker Failure

Protection, and general-purpose logic timers. Setting Groups and Virtual Control Switches make up the

control functions. The following paragraphs describe each protection and control function.

Overcurrent Protection

Phase and one neutral instantaneous overcurrent elements (50TP and 50TN) with settable time delays

provide inadvertent energization protection when properly supervised by voltage and/or frequency

elements (381. 159. 127).

One phase time-overcurrent element can be voltage restrained (51/27R) or voltage controlled (51/27C) to

provide system backup overcurrent protection (51P).

Two neutral inverse time-overcurrent elements provide ground overcurrent protection and/or generator

step-up (GSU) transformer ground backup protection (51TN and 151TN).

Each neutral 50/51 element can be assigned to monitor either the three-phase residual (IN

) or the optional

independent ground input (IG

).

One inverse time, negative sequence overcurrent element provides generator unbalance overload

protection (46).

Time-overcurrent functions employ a dynamic integrating timing algorithm covering a range from pickup to

40 times pickup with selectable instantaneous or integrated reset characteristics.

Time-overcurrent curves conform to the IEEE C37.112 document and include seven curves similar to

Westinghouse/ABB CO curves, five curves similar to GE IAC curves, four IEC curves, a fixed time curve,

and a user programmable curve. Each time current characteristic can be set for integrating or

instantaneous reset.

Digital signal processing filters out unwanted harmonic components while providing fast overcurrent

response with limited transient overreach and over-travel.

Voltage Protection

One volts per hertz protective element provides overexcitation protection for a generator and/or GSU

transformer (24).

Two phase overvoltage and two phase undervoltage element provides over/undervoltage protection (27P,

127P, 59P, and 159P). Phase overvoltage protection can be set for one of three, two of three, or three of

three logic. When a four-wire voltage transformer connection is used, overvoltage protection can be set

for either phase-to-phase voltage or phase-to-neutral voltage.

Two auxiliary overvoltage and two auxiliary undervoltage elements provide over/undervoltage protection

(27X, 127X, 59X, and 159X). Auxiliary voltage protection elements can be set to individually monitor the

auxiliary voltage fundamental, third harmonic, or phase 3V0 voltages. Complete stator ground fault

protection is provided when the auxiliary voltage input is connected to the generator grounding resistor

voltage, the 27X element is set for third harmonic undervoltage, and the 59X is set for the auxiliary

voltage fundamental.

With the auxiliary voltage input connected to the bus, one sync-check function provides synchronism

protection when putting the generator online (25). Sync-check protection checks for phase angle

difference, magnitude difference, frequency difference (slip) and, optionally, if the generator frequency is

greater than the bus frequency.

One negative-sequence overvoltage element provides protection for phase unbalance or a reverse

system phase (47).

Voltage transformer circuit monitoring adds security by detecting problems in the voltage transformer

sensing circuits and preventing misoperations of the 27P, 127P, 47. 59P, 159P, and the 51/27 functions

(60FL).

Directional Power Protection

Two directional power elements provide loss of prime mover protection and/or sequential trip, shutdown

operation (32. 132). Each directional power element can be set individually for forward or reverse power.

The power measurement algorithm is adapted as appropriate for any possible three-phase or single

phase voltage transformer connection. Directional Power is calibrated on a three-phase basis regardless

of the voltage transformer connection used.

Frequency Protection

Four over/underfrequency protection function blocks are provided: 81. 181. 281. and 381. Each function

block can be set for overfrequency or underfrequency operation.

Loss of Excitation

Loss of excitation protection consists of two elements (40Q, 140Q) that use offset sloped var flow

algorithm.

Breaker Failure Protection

One breaker failure protection block (BF) provides programmable breaker failure protection.

General Purpose Logic Timers

Four general-purpose logic timers (62. 162. 262. and 362) with six modes of operation are provided.

Setting Groups

Two setting groups allow adaptive relaying to be implemented to optimize BE1-GPS100 settings for

various operating conditions. Setting group selection can be made via relay logic, 43 auxiliary switches,

and hard-wired inputs.

Virtual Control Switches

BE1-GPS100 virtual control switches include one virtual breaker control switch and four virtual switches.

Trip and close control of a selected breaker can be controlled by the virtual breaker control switch (101).

The virtual breaker control switch is accessed locally from the front panel human machine interface (HMI)

or remotely from the communication ports.

Additional control is provided by the four virtual switches: 43. 143. 243. and 343. These virtual switches

are accessed locally from the front panel HMI or remotely from the communication ports. Virtual switches

can be used to trip and close additional switches or breakers, or enable and disable certain functions.

Metering Functions

Metering is provided for all measured currents, voltages, and frequency and all derived neutral and

negative-sequence currents and voltages. Three phase watts, vars, and power factor is provided. Per

phase watts and vars is also provided when the VT connection is 4W.

Reporting and Alarm Functions

Several reporting and alarm functions provide fault reporting, demand, breaker, and trip circuit monitoring,

as well as relay diagnostic and firmware information.

Energy Data Reporting

Energy information in the form of watt-hours and var-hours is measured and reported by the BE1

GPS100. Both positive and negative values are reported in three-phase, primary units.

Relay Identification

Two free-form fields are provided for the user to enter information to identify the relay. These fields are

used by many of the reporting functions to identify the relay that the report is from. Examples of relay

identification field uses are station name, circuit number, relay system, purchase order, and others.

Clock

A real-time clock is included with a capacitor backup and is available with an optional battery backup.

Depending upon conditions, capacitor backup maintains timekeeping during an eight to 24 hour loss of

operating power. Battery backup maintains timekeeping when operating power is removed for five years

or longer.

IRIG

A standard IRIG input is provided for receiving time synchronization signals from a master clock.

Automatic daylight saving time compensation can be enabled. Time reporting is settable for 12 or 24-hour

format. The date can be formatted as mm/dd/yy or dd/mm/yy.

General Status Reporting

The BE1-GPS100 provides extensive general status reporting for monitoring, commissioning, and

troubleshooting. Status reports are available from the front panel HMI or communication ports.

Demand Reporting

Ampere demand registers monitor phase A, B, C, Neutral, ±Power (kW), ±Reactive Power (kvar), and

Negative-Sequence values. The demand interval and demand calculation method are independently

settable for phase, neutral, and negative measurements. Demand reporting records today’s peak,

yesterday’s peak, and peak since reset with time stamps for each register.

Breaker Monitoring

Breaker statistics are recorded for a single breaker. They include the number of operations, accumulated

interrupted I or I2. and breaker time to trip. Each of these conditions can be set to trigger an alarm.

Trip Circuit Monitoring

A trip circuit monitor function is provided to monitor the trip circuit of a breaker or lockout relay for loss of

voltage (fuse blown) or loss of continuity (trip coil open). The monitoring input is internally connected

across OUT1. Additional trip or close circuit monitors can be implemented in BESTlogic using additional

inputs, logic timers, and programmable logic alarms.

Fault Reporting

Fault reports consist of simple target information, fault summary reports, and detailed oscillography

records to enable the user to retrieve information about disturbances in as much detail as is desired. The

relay records and reports oscillography data in industry standard IEEE Comtrade format to allow using

any fault analysis software. Basler Electric provides a Windows® based program called BESTwave™ that

can read and plot binary or ASCII format files that are in the COMTRADE format.

Sequence of Events Recorder

A 255 event Sequence of Events Recorder (SER) is provided that records and time stamps all relay

inputs and outputs as well as all alarm conditions monitored by the relay. Time stamp resolution is to the

nearest half-cycle. I/O and Alarm reports can be extracted from the records as well as reports of events

recorded during the time span associated with a specific fault report.

Alarm Function

Extensive self-diagnostics will trigger a fatal relay trouble alarm if any of the relay core functions are

adversely affected. Fatal relay trouble alarms are not programmable and are dedicated to the Alarm

output (OUTA) and the front panel Relay Trouble LED. Additional relay trouble alarms and all other alarm

functions are programmable for major or minor priority. Programmed alarms are indicated by major and

minor alarm LEDs on the front panel. Major and minor alarm points can also be programmed to any

Leave a Reply

Your email address will not be published. Required fields are marked *