Woodward: CONTROL-LS-511-5/P1 8440-2152 Circuit Breaker Control & Protection
Woodward: CONTROL-LS-511-5/P1 8440-2152 Circuit Breaker Control & Protection
New Features
Two breaker control variants
Separate incoming and outgoing
current inputs per phase
German grid code compliance
(VDE AR-N 4105 & BDEW)
Enhanced diagnostics and
visualization
Designed as a compact
solution for complex power
management applications
Up to 16 LS-5 units can be
utilized in one application
Up to 32 bus segments are
possible
Synch check and mains
decoupling in one compact
controller
Adjustable vector groups for
synchronization
Utility import/export control
Automatic and Manual mode
LS-5 “Stand alone” mode
for use without easYgen
3400XT/3500XT System
LogicsManager functionality
for application customization
CAN and RS-485 interfaces for
remote control and
visualization purposes
True RMS sensing
Available as cabinet front door
mounted device or
DIN-Rail back panel mounted
metal housing
Freely configurable relay
outputs
Freely configurable discrete
inputs
QV monitoring
Time-dependent voltage
monitoring
RoHS2. BDEW and VDE AR-N
4105 compliant
8440-2152
Power supply …………………………………………………. 12/24 Vdc (8 to 40 Vdc)
Intrinsic consumption ………………………………………….. max.~ 5 W (LS-511)
……………………………………………………………………….. max..~ 6 W (LS-521)
Ambient temperature (operation) ………………….. -20 to 70 °C / -4 to 158 °F
Ambient temperature (storage) …………………… -30 to 80 °C / -22 to 176 °F
Ambient humidity……………………………………………… 95 %, non-condensing
Voltage ………………………………………………………………………………….. ( /)
120 Vac [1] Rated (Vrated) …………………………………….. 69/120 Vac
Max. value (Vmax) …………………………………….. 86/150 Vac
Rated voltage phase – ground ………………………. 150 Vac
Surge volt.(Vsurge) ……………………………………………. 2.5 kV
and 480 Vac [4] Rated (Vrated) …………………………………… 277/480 Vac
Max. value (Vmax) …………………………………… 346/600 Vac
Rated voltage phase – ground ………………………. 300 Vac
Surge volt.(Vsurge) ……………………………………………. 4.0 kV
Accuracy ……………………………………………………………………………… Class 1
Linear measuring range …………………………………………………….. 1.25×Vrated
Measuring frequency……………………………………….. 50/60 Hz (30 to 85 Hz)
High Impedance Input; Resistance per path ……. [1] 0.498 M, [4] 2.0 M
Current (Isolated) Rated (Irated) ………………………… [1] ../1 A or [5] ../5 A
Linear measuring range ……………………………………………….. Igen = 1.5×Irated
Burden ……………………………………………………………………………… < 0.15 VA
Rated short-time current (1 s) ……………………………[1] 50×Irated, [5] 10×Irated
Discrete inputs …………………………………………………………………… isolated
Input range ……………………………………………………. 12/24 Vdc (8 to 40 Vdc)
Input resistance …………………………………………………….. approx. 20 kOhms
Relay outputs …………………………………………………………………. potential free
Contact material ……………………………………………………………………….. AgCdO
Load (GP) ……………………………………………………… AC: 2.00 Aac@250 Vac
DC: 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Pilot duty (PD) ……………………………………………………………………… AC: B300
DC: 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Housing (LS-521) Front door mounting ……………………….. Plastic housing
Dimensions WxHxD …………………………………… 219 × 171 × 61 mm
Front cutout WxH …………………………. 186 [+1.1] × 138 [+1.0] mm
Connection ………………………………………………. screw/plug terminals 2.5 mm²
Front ………………………………………………………………………… insulating surface
Sealing Front ……………………………. IP66 (with screw fastening)
Front ……………………………. IP54 (with clamp fastening)
Back ……………………………………………………………. IP20
Weight …………………………………………………………………………….approx. 850 g
Housing (LS-511) Back panel mounting……………….. Sheet metal housing
Dimensions WxHxD …………………………………… 190 × 167 × 47 mm
Connection ………………………………………………. screw/plug terminals 2.5 mm²
Protection system ……………………………………………………………………….. IP 20
Weight (plastic/sheet metal) ………………………………………. approx. 850/840 g
Disturbance test (CE) ………… tested according to applicable EN guidelines
Listings ………………………………. CE, UL/cUL, BDEW, VDE AR-N 4105. EAC
Marine ……………………………………………………………………. Pending: LR, ABS