ABB

ABB REF630 UBFNAAABBBAZANBBXB Feeder Protection and Device

ABB REF630   UBFNAAABBBAZANBBXB  Feeder Protection and Device

Overview

REM630 is a comprehensive motor management relay for protection, control,

measuring and supervision of medium and large synchronous and asynchronous

motors in medium voltage industrial power systems. REM630 is a member of ABB’s

Relion® product family and a part of its 630 series characterized by functional

scalability and flexible configurability. REM630 also features necessary control

functions required for the management of industrial motor feeder bays. The protection

relay can be used with both circuit-breaker controlled and contactor controlled drives.

The supported communication protocols including IEC 61850 offer seamless

connectivity to industrial automation systems.

REF630

Product version history

Product version

Product history

First release

• Support for IEC 60870-5-103 communication protocol

• Analog GOOSE

• RTD module

• New analog input modules

• Stabilized three-phase differential protection for motors and generators

• High-impedance/flux-balance-based differential protection for motors

and generators

• Synchronized motor protections

No new functions

• Operation time counter

• Comparison functions

• AND and OR gates with 20 inputs

PCM600 and IED connectivity package version

• Protection and Control IED Manager PCM600 Ver. 2.5 or later

• ABB REM630 Connectivity Package Ver. 1.3 or later

• Application Configuration

• Parameter Setting

• Signal Matrix

• Signal Monitoring

• Disturbance Handling

• Event Viewer

• Graphical Display Editor

Hardware Configuration

• IED Users

• IED Compare

• Communication Management

• Configuration Migratio

Product variants

The IED capabilities can be adjusted by selecting a product variant. The IED

capabilities can be extended by adding HW and/or SW options to the basic variant. For

example, the physical communication connector can be either an electrical or optical

Ethernet connector.

The number of binary inputs and outputs depends on the amount of the optional BIO

modules selected. For a 4U IED, it is possible to take 2 additional BIO modules at the

maximum, and for a 6U IED, it is possible to take 4 additional BIO modules at the

maximum.

• Basic variant: 14 binary inputs and 9 binary outputs

• With one optional BIO module: 23 binary inputs and 18 binary outputs

• With two optional BIO modules: 32 binary inputs and 27 binary outputs

• With three optional BIO modules: 41 binary inputs and 36 binary outputs

• With four optional BIO modules: 50 binary inputs and 45 binary outputs

Optional functions

Some of the available functions are optional, that is, they are included in the delivered

product only when defined by the order code.

• Frequency protection

• Overfrequency protection

• Underfrequency protection

• Frequency gradient

• Phase sequence voltage functions

Positive-sequence overvoltage protection

• Positive-sequence undervoltage protection

• Negative-sequence overvoltage protection

• Stabilized differential protection for motors

• Additional functions for synchronous motor

• Reverse power/directional overpower protection

• Three-phase underexcitation protection

• Rotor E/F protection

Physical hardware

The mechanical design of the IED is based on a robust mechanical rack. The HW

design is based on the possibility to adapt the HW module configuration to different

customer applications.

Table 2:

IED contents

Content options

LHMI

Communication and

CPU module

Auxiliary power/binary

output module

1 electrical Ethernet connector for the detached LHMI module (the connector

must not be used for any other purpose)

1 Ethernet connector for communication (selectable electrical or optical

connector)

IRIG-B (external time synchronization) connector

1 fibre-optic connector pair for serial communication (selectable plastic or

glass fibre)

14 binary control inputs

48-125 V DC or 100-240 V AC/110-250 V DC

Input contacts for the supervision of the auxiliary supply battery level

3 normally open power output contacts with TCS

3 normally open power output contacts

1 change-over signalling contact

3 additional signalling contacts

1 dedicated internal fault output contact

Analog input module

4. 7 or 8 current inputs (1/5 A)

4. 3 or 2 voltage inputs (100/110/115/120 V)

With 4 current inputs (1/5 A) also max. 1 accurate current input for sensitive

earth fault protection (0.1/0.5 A)

ABB 07BR61R1   GJV3074376R1
ABB 6231BP10910
ABB TU847   3BSE022462R1
ABB 5SHY35L4520   5SXE10-0181 AC10272001R0101
ABB PM825   3BSE010796R1
ABB PFEA112-20   3BSE030369R0020
ABB CI858-1   3BSE018137R1
ABB PFTL201C   10KN 3BSE007913R0010
ABB DSAI133A  3BSE018290R1
ABB DSAI133A   3BSE018290R1
ABB PFSK142   3BSE006505R1
ABB 216DB61   HESG324063R100/J
ABB 216EA62   1MRB150083R1/F 1MRB178066R1/F
ABB UNS4881b,V4   3BHE009949R0004
ABB UNS2882A   3BHE003855R0001
ABB UNS0887A-P   3BHE008128R0001
ABB UNS2880b-P,V2   3BHE014967R0002
ABB UNS2881b-P,V1   3BHE009319R0001

Leave a Reply