YOKOGAWA

YOKOGAWA F3WD64-3N Input-output module

The F3SC21-1N (FA-M3 Value) is a compact programmable controller

consisting of the following modules:

 F3BU04-0N base module (with 4 slots)

 F3SP05-0P sequence CPU module (with power supply and

memory)

 F3WD64-3N I/O module (with 32 inputs and 32 outputs)

The F3SP05-0P double-slot sequence CPU module is installed in the

leftmost slot of the F3BU04-0N 4-slot base module and the

F3WD64-3N I/O module in slot 2. You can install any FA-M3 I/O

modules in slots 3 and 4.

ASSY  S926 BK-0 

PROGRAMMER

 Features

 Its compact size greatly reduces installation space.

 The sequence CPU module has a 100-240 VAC universal power

supply so that the user doesn’t have to worry about the power

supply environment when using the F3SC21-1N.

 The high-speed instruction processing capability of the

F3SC21-1N makes it ideal for applications that require high speed

response.

 The use of a structured ladder programming language facilitates

programming and maintenance of ladder programs.

 The sequence CPU module has the personal computer link

function to communicate with a higher-level computer or display.

The user needs no personal computer link module (F3LC11-1N)

for this purpose.

 Programs and data can be saved on an optional ROM pack.

Number of slots 4

Number of free I/O slots 2 (as the sequence CPU and 64-point I/O modules occupy two slots) Base module

(F3BU04-0N)

Weight 140 g

Supply voltage 100-240 V AC, single phase, 50/60 Hz

Supply voltage fluctuation range 85-264 V AC, 50/60 Hz ±3 Hz

Power consumption 35 VA

Inrush current 20 A max. (120 V AC, Ta=25 ºC)

45 A max. (240 V AC, Ta=25 ºC)

Rated output voltage 5 V DC

Rated output current 2.0 A

Insulation resistance 5 MΩ or greater at 500 V DC (between external AC terminals and FG terminal)

Dielectric strength 1500 V AC for 1 minute (between external AC terminals and FG terminal)

FAIL-signal contact output Provided on the front terminal block on the power supply block; contact rating:

24 V DC, 0.3 A (both normally-open and normally-closed terminals available)

Allowable common-mode

voltage of FAIL-signal contact

120 V max. AC or DC

(between FAIL OUTPUT COM terminal and FG terminal)

Leakage current 0.5 mA max.

Allowable momentary power

failure time 20 ms

Power supply block

Noise immunity Immune to noise of up to 1500 Vp-p with 1-s pulse width and 1-ns rise time at 25-60

Hz (as measured with a noise simulator).

Control mode Stored program, cyclic execution

I/O control mode Refreshing method/direct I/O instructions

Programming language Structured ladder language, mnemonic language

Basic instructions 25 types Number of

instructions Application

instructions 227 types

Basic instructions 0.18-0.36 μs/instruction Instruction

processing

speed Application

instructions 0.36 μs min./instruction

Program size 5K steps (can be stored in ROM)

Number of I/O points 2048 points max.

Number of program blocks 32 max.

Sampling trace No

Link to personal computer Yes

Monitoring of scan time 10-200 ms variable

Internal relay I: 4096 points max.

Shared relay —

Extended shared relay —

Link relay L: 2048 points

Special relay M: 2048 points

Timer T: 512 points max. (total of internal and external timers and counters)

Counter C: 512 points max. (total of internal and external timers and counters)

Data register D: 5120 points max.

File register —

Link register W: 2048 points

Special register Z: 512 points

Index register V: 32 points

Shared register —

Devices

Extended shared register —

Sequence

CPU module*1

(F3SP05-0P)

Sequence CPU block

Self-diagnostics Memory error, CPU error, input/output error, syntax check, etc.

Other features

 Configuration function (device capacity, data lock-up range at power failure, output

when CPU stops, etc.)

 Constant scan function (1 ms to 190 ms)

 Debugging functions (forced SET/RESET, online edit, scan operation, etc.)

 Error history function (64 records)

 Date/clock function (year/month/day/hour/minute/second/day of week)

 Program protection functions

 ROM programming and data storage

 Personal computer link function

Sequence

CPU block

Current consumption 350 mA (5 V DC)*2

External dimensions 58 (W) X 100 (H) X 83.2 (D) mm

Weight 320 g

UL UL508 approved, File No.E188707

(Overvoltage Category*4 II, Pollution Degree*5 2)

CE EMC

Directive

EN 61326-1 Class A, Table 2 (For use in industrial locations)

EN 61326-2-3*6

EN 55011 Class A, Group 1

EN 61000-6-2. EN 61000-3-2. EN 61000-3-3  compliance

Sequence

CPU module*1

(F3SP05-0P)

Common

Compliance

with

safety and

EMC

standards*3

C-Tick EMC

Framework EN 55011 Class A, Group 1 compliance

Input type DC voltage

Number of points 32

Number of points/common 8 points/common

Isolation method Photocoupler isolation

Rated input voltage 24 V DC

Operating voltage 20.4-26.4 V DC

Rated input current 4.1 mA/point (24 V DC)

ON 6.0 V DC min., 3.2 mA min. Operating

voltage/current OFF 5.8 V DC max., 0.9 mA max.

OFF→ON 1.0 ms max. Input

ON→OFF 2.5 ms max.

Input Block

Interrupt No

Output type Transistor contact (sink type)

Number of points 32

Number of points/common 8 points/common

Isolation method Photocoupler isolation

Rated load voltage 24 V DC

Maximum load current 0.1 A/point, 0.4 A/common

OFF→ON 1.0 ms max. Output

Response ON→OFF 1.0 ms max.

Off-time leakage current 0.1 mA max.

Surge protector Zener diode

Output Block

External power supply 24 V DC, 60 mA

Input/output status indicator Lit when on (indicates either input or output status by using the selector switch)

Current consumption 200 mA (5 V DC)

External connection Two 40-pin connectors

Input/Output

module

(F3WD64-3N)

Common

Weight 160 g

*1: When a sequence CPU module is to be used, use the Ladder Diagram Support Program M3. Rev. 2.02 or later.

*2: The total current dissipated by the modules in slots 3 and 4 must be less than 1400 mA.

*3:  For details on conforming modules, see “UL-approved, CE marking and C-Tick mark-compliant Modules” (GS 34M06C11-21E) general specification

brochure.

*4: The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four categories.

Overvoltage Category II applies to systems with rated voltage of 220/230/240V and applies to electrical appliances, portable devices, etc.

*5:  The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a reduction of dielectric

strength or surface resistivity in the operating environment of the equipment.  Pollution degree 2 refers to an environment where normally only

non-conductive pollution occurs but occasionally temporary conductivity caused by condensation is to be expected.

*6: EN 61326-2-3 is applicable only to F3CU04-0S and F3CU04-1S