Honeywell

H0NEYWELL 05701-A-0502 Rack

Introduction

System 57 is a fire and or gas control system offering great flexibility through its modular

construction. The system is constructed in a rack that can be fitted with fire and/or gas

control cards and corresponding interface cards that allow connection of the associated

detectors. The rack can be panel or cabinet mounted. Further details of the main

components are given below. A graphical overview of all the available components and how

they can be assembled into a system is shown in section X. For further detailed information

refer to the individual operating manuals 05701-M-5001 (5701 gas control card), 05704-M

5001 (5704 gas control card) and 05704-M-5002 (fire control card).

3.1 Gas Control Cards

The System 57 gas control cards provide display and alarm facilities for the full range of

Sieger gas detectors. Their back lit, multi-part LCD displays the gas reading and status in

both analogue bar graph and digital numeric forms. In addition, there is an alpha numeric

message section to give detector (and engineering function) status.

There is a choice of either the single channel 5701 or the four channel 5704 gas control

cards. Each card has two input options; one is for catalytic bridge type while the other is for 4

to 20mA detectors or transmitters. The control cards feature 3 levels of alarm, options of

individual, zoned, voted, master, time delayed, update and rate of rise alarm facilities, 4 part

LCD display, peak reading facility and detector performance monitoring.

3.2 Fire Control Cards

The 5704F fire control cards provide display and alarm facilities for a wide variety of fire

detection products and provide up to four fire zone inputs compatible with most flame,

smoke and heat detectors and manual call points. The status of each fire zone is individually

displayed by high intensity LEDs. In addition, each card has two line monitored alarm output

circuits. Both fire and gas control cards can be freely mixed in a rack. Up to 60 fire zones

can be monitored per 19″ rack.

Each rack that contains a 5704F fire card has one 5704FS fire status panel fitted. The

5704FS fire status panel provides common display and alarm indication for all of the fire

cards in a rack as well as a local audible sounder. It also provides common push buttons for

executing specific fire card related functions.

3.3 Master Alarm Update Panel

The master alarm update facility can be enhanced by adding the optional master alarm

update panel which enables update facilities without the need for external wiring. The alarm

update panel is 1″ wide and provides audible and visual alarms and a reset and accept push

button.

3.4 Power Supply Units

The power supply units are rack mounted to match the main control card rack design. The

units are 1U high, and available in 19″ & ½ 19″ sizes. Total maximum power capability is

200W (built in 50W blocks). The input voltage is auto sensing (AC or DC) and the output is

regulated DC with over voltage and overload protection.

3

System 57 Quick Start Guide

05701-M-5026 MAN0839 Issue 1

3.5 Engineering Card

The System 57 engineering card provides full maintenance and set up facilities for each

channel card. The front panel has a series of tactile feedback push buttons that allows

checks of the alarm levels and performance to be carried out for each channel. A real-time

‘on board’ clock provides calibration history and calibration overdue reminder functions. An

access key provides security protection.

The engineering card can be fitted with optional modules for extended system options.

3.5.1 Serial Communications Module

The serial communications module provides a gateway between the System 57 rack and a

remote device (DCS, PLC or SCADA package) to allow the continuous monitoring of each

channel’s operation and condition as well as allowing remote configuration of the system

operation. The module uses the industry standard MODBUS RTU protocol, RS485/422/232

standard. Custom designed SCADA graphics packages are also available.

3.5.2 RS232 Printer Driver Module

The printer driver module provides a serial output in the event of a gas alarm, fault or user

intervention. The output is RS232 ASCII event data, has selectable print criteria, provides

time and date stamping and is electrically isolated.

3.5.3 Master Alarm Update Module

The alarm update module provides a common alarm indication with new alarm event update.

It also provides 2 Outputs: 1 relay, 1 Darlington, with selectable operation: pulsed or

continuous and an alarm and common alarm reset input. It complies with ISA ‘M’, DIN 19

235. It can be used with the optional master alarm update panel.

3.6 Interface Cards

There are 9 versions of interface card available (5 for 5701 Gas, 2 for 5704 Gas and 2 for

5704 Fire Control Cards). The interface cards provide the link between the various fire or

gas detectors and the control cards. They provide detector interface, offer flexib