GE

GE HE693RTD600

HE693RTD600

The HE693RTD600 allows RTD temperature sensors to be connected to the PLC directly without external signal processing such as transducers, transmitters, etc.

All analog and digital processing on the module is performed on the HE693RTD600.

and temperature values in 0.5°C or 0.5°F increments are written to the 90-30 %AI input table.

All modules feature six channels, and support PT-90 (MIL-7990), PT-100 (alpha=.00385. . 003902 and . 03906), Ni-120. Cu-10. Cu-50. Cu-53. Cu-100. Pt-1000. TD5R and Linear Resistance.]

HE693RTD600

Technical Specifications

Power Consumption (Typical)    75mA @ 5VDC

Number of Channels    6

I/O Points Required    6%AI

Input Impedance    >1000 Meg Ω

Fault Protection    Zener Diode Clamp

A/D Conversion Type    16 bit, Integrating

Update Time    50 Channels per second

Average RTD current, PT-100    330 microamps

Channel to Channel Tracking    0.1°C

Resolution    0.1°C

Accuracy    ± 0.5°C typical, ± 1.0°C for Cu-10 and TD5R

Operating Temperature    0 to 60°C (32° to 140°F)

Relative Humidity    5% to 95% non-condensing

HE693RTD600

Leave a Reply

Your email address will not be published. Required fields are marked *