Foxboro DCS Compact FBM241/c/d, Redundant, Discrete I/O Modules
Foxboro DCS Compact FBM241/c/d, Redundant, Discrete I/O
Modules
The Compact FBM241. FBM241c, and FBM241deach have eight discrete inputs and
eight discrete outputs available as a single or redundant module. A redundant pair of
the modules combine to provide redundancy at the FBM level with field I/O wired to
one commontermination assembly.
The Compact Channel Isolated, Discrete I/O Interface Modules (Compact FBM241/c/
d) have eight discrete input channels and eight discrete output channels. Associated
termination assemblies (TAs) support discrete input or output signals at voltages of
under 60 VDC, 120 VAC/125 VDC, or 240 VAC.
Depending on the type of I/O signal required, the TAs contain current limiting devices,
fuses, relays, or relay outputs with internal or external power source and fusing.
The module is available in three distinct types and each type with its associated TA
supports the following discrete inputs and outputs:
Each type of Fieldbus Module (FBM), without signal conditioning, uses a 15 to 60
VDCinput or output signal. Each discrete input and output is galvanically isolated
from other channels and ground. When used with external excitation, each discrete
input and output is group isolated.
The module performs signal conversion required to interface electrical input signals
from field sensors to the optionally redundant fieldbus. It executes the Discrete I/O or
Ladder Logic program, with the following configurable options: Input Filter Time, Fail
Safe Configuration, Fail-Safe Fall-Back, and Sustained or Momentary Outputs. If the
Momentary Output configuration is selected, then Pulse Output Interval is also
configurable
FBM241
Features
• 8discrete inputs
• 8discrete outputs
• Single or Redundant Module
• Supports discrete inputs/output signals at voltages of:
◦ 15to60VDC
◦ 120VAC/125VDC
◦ 240VAC

FBM241
• Eachinput and output is galvanically isolated: group isolated when used with
external excitation
• Compact,rugged design suitable for enclosure in Class G3 (harsh) environments
• Executes the Discrete I/O or Ladder Logic program, with the following
configurable options: Input Filter Time, Fail Safe Configuration, Fail-Safe Fall
Back, and Sustained or Momentary Outputs
• Various Termination Assemblies (TAs) that contain:
◦ Current limiting devices
◦ Fuses
◦ Relayoutputs
◦ Relayoutputs with internal or external power source and fusing
◦ Solid state outputs
Redundant Outputs
Aredundant contact output function block, COUTR, is used for each redundant pair of
outputs. The COUTR block handles output writes and initialization logic for the
redundant channels. On each write of the COUTR block, identical output writes are
sent to both modules, fully exercising the Fieldbus and the logic circuitry of each
module. You can select a sustained output that follows the block input or a pulsed
output with a selectable pulse width.
Whenafailure is detected in the modules, its output is marked as BAD and the
corresponding channel in the good module automatically continues to drive the
discrete outputs. Each output channel drives an externally powered load. Power for
each Compact FBM241 module is diode OR’d together in the redundant adapter to
help assure redundant power. The microprocessor of each module executes the
digital output application program, plus diagnostic routines that validate the health of
the FBM.