EMERSON KJ4001X1-NA1 12P3373X012 REV:C 1-Wide I/O Carrier Extender Right
EMERSON KJ4001X1-NA1 12P3373X012 REV:C 1-Wide I/O Carrier Extender Right
KJ4001X1-NA1 1-Wide I/O Carrier Extender
Right
Hazardous Atmosphere
II 3G Ex ec IIC Gc
FM16ATEX0056U
FM21UKEX0017U
CL. I Div. 2 GP. A,B,C,D
CL. I Zone 2 AEx/Ex ec IIC Gc
FM17US0286U
FM17CA0145U
Power Specifications
Local Bus Power
12 VDC at 8 A
Environmental Specifications
Ambient
Temperature
Shock
Vibration
Airborne
Contaminants
KJ4001X1-NA1

KJ4001X1-NA1
Relative Humidity -40°C to +70°C
10g ½ Sinewave for 11msec
1mm Peak to Peak from 2 to 13.2Hz;
0.7g from 13.2 to 150Hz
ISA-S71.04 –1985 Airborne
Contaminants Class G3
5 to 95% Non-Condensing
Note: Refer to the product label for serial number
and location and date of manufacture.
Warning: This product has specific instructions for
installation, removal and operation in hazardous
areas. Refer to document 12P2046 “DeltaV™
Scalable Process System Zone 2 Installation
Instructions”. Other installation instructions are
available in the “DeltaV™ M-Series Hardware
Installation and Reference” manual.
Removal and Insertion
This unit cannot be removed or inserted with system
power energized. Power must be de-energized
before disconnecting any carriers or LocalBus
Extender cables.
No combination of I/O carriers and LocalBus
Extenders must exceed a length of 6.5 meters.
Interconnecting cable between enclosures must be
in conduit.
Maintenance and Adjustment
This unit contains no user serviceable parts and
should not be disassembled for any reason.