Woodward

Woodward easYgen-3500XT-P2-LT-RENTAL 8440-2291 Genset Control for

Woodward easYgen-3500XT-P2-LT-RENTAL 8440-2291  Genset Control for

Genset Control for

Complex Paralleling Operation

New Features

✓ Built-In Redundant Ethernet

✓ Power Measurement Class 1

✓ Direct Connect Up to 690 VAC

✓ AnalogManager & Editable Screens

✓ Multi-Interface ToolKit connectivity

✓ Face plate with tactile buttons

✓ Drop-In replacement

Premium genset control

for complex paralleling

applications of up to 32

gensets in

• Prime Power &

Cogeneration (CHP)

• Peak shaving

operation

• Emergency operation

• Import/Export

operation

• Islanded & Utility

parallel operation

• Group controller and LS

6XT support to manage

large fleet of gensets and

circuit breakers

• Run-Up Synchronization

• Built-in active voltage

regulation

• Complete engine,

generator and utility

protection

• Up to 9 communication

ports: 3xEthernet, 3xCAN

(CANOpen and J1939),

RS-485. USB, Interface

expansion card

• Customizable logic, HMI

screens, and alarms

• Dedicated low

temperature display

variants

• UL 61010. UL 6200. CSA,

RoHS 2. and marine

easYgen-3400XT3500XT

(ABS, LR) compliance

Power supply ………………………………………………….12/24 VDC (8 to 40 VDC)

Intrinsic consumption ……………………………….  max. 22 W (LT: max.32 W)

Ambient temperature (operation) …………… -20 to 70 °C (LT: -40 to 70 °C)

Ambient temperature (storage) …………………. -30 to 80 °C / -22 to 176 °F

Ambient humidity…………………………………………….. 95%, non-condensing

Voltage (software configurable) …………………………………………….. ( /)

100 VAC  Rated (Vrated) …………………………………….. 69/120 VAC

Max. value (Vmax) …………………………………….. 86/150 VAC

and 400 /600 VAC  Rated (Vrated)* …………………………………… 400/690 VAC

Max. value (Vmax) …………………………………… 520/897 VAC

Rated surge volt. (Vsurge) ……………………………………………. 6.0 kV

Accuracy …………………………………………………………………………. Class 0.5

Measurable alternator windings . 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w

Setting range ………………. primary …………………………… 50 to 650.000 VAC

Linear measuring range …………………………………………………… 1.25×Vrated

Measuring frequency …………………………………….. 50/60 Hz (30 to 85 Hz)

High Impedance Input; Resistance per path …………………………… 2.5 M

Max. power consumption per path ………………………………………. < 0.15 W

Current (Isolated, software configurable)     Rated (Irated) ……… 1A or 5A

Linear measuring range ……………………………………………… Igen = 3.0×Irated

Imains/ground = 1.5×Irated

Setting range ……………………………………………………………… 1 to 32.000 A

Burden ……………………………………………………………………………. < 0.10 VA

Rated short-time overcurrent (1 s) ……………………[1] 50×Irated, [5] 10×Irated

Accuracy ………………………………………………………………………… Class 0.5

Power ……………………………………………………………………………………………

Setting range ……………………………………………….. 0.5 to 99.999.9 kW/kvar

Accuracy …………………………………………………………………………. Class 1.0

Discrete inputs …………………………………………………………………… isolated

Input range ……………………………………………………12/24 VDC (8 to 40 VDC)

Input resistance …………………………………………………… approx. 20 kOhms

Transistor outputs (P2 only) ………………………………………………… isolated

Rated switching voltage ………………………………………………… max. 24 VDC

Maximum switching voltage …………………………………………………… 40 VDC

Maximum switching current ……………………………………………. 300 mA DC

Isolation Test voltage (<1s) ………………………………………………….. 500 VAC

Isolation voltage (continuously) …………………………………………. 100 VAC/DC

Relay outputs ……………………………………………………………………… isolated

Contact material ………………………………………………………………….. AgCdO

Load (GP) …………………………………………………………… 2.00 AAC@250 VAC

2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC

Analog inputs (isolated) …………………………………………………freely scalable

Type 1 ………………………………………. 0 to 1 V / 0 to 2000 Ohms /